Mitsubishi Electronics FR-A701 Marine Battery User Manual


 
62
Before operation
4.3.7 Selection of the start command and frequency command locations (Pr. 79)
*1 The priorities of the frequency commands when Pr. 79 = "3" are "Multi-speed operation (RL/RM/RH/REX) > PID control (X14) > terminal 4 analog
input (AU) > digital input from the operation panel".
*2 For the terminal used for the X12 signal (PU operation interlock signal) input, set "12" in Pr. 178 to Pr. 189 (input terminal function selection) to assign
functions.
For Pr. 178 to Pr. 189, refer to Chapter 4 of the Instruction Manual (Applied).
When the X12 signal is not assigned, function of the MRS signal switches from MRS (output stop) to PU operation interlock signal.
Select the start command location and frequency command location.
Parameter
Number
Name
Initial
Value
Setting
Range
Description
LED Indication
: Off
: On
79
Operation
mode
selection
0
0
Use External/PU switchover mode (press to switch
between the PU and External operation mode. (Refer to
page 83))
At power on, the inverter is in External operation mode.
PU operation mode
External operation mode
NET operation mode
1 Fixed to PU operation mode
PU operation mode
2
Fixed to External operation mode
Operation can be performed by switching between the
external and NET operation mode.
External operation mode
NET operation mode
3
External/PU combined operation mode 1
External/PU combined
operation mode
Frequency command Start command
PU (FR-DU07/FR-PU04/
FR-PU07) setting or
external signal input (multi-
speed setting, across
terminals 4-5 (valid when
AU signal turns on)).
*1
External signal input
(terminal STF, STR)
4
External/PU combined operation mode 2
Frequency command Start command
External signal input
(Terminal 2, 4, 1, JOG,
multi-speed selection, etc.)
Input from the PU (FR-
DU07/FR-PU04/FR-PU07)
(, )
6
Switchover mode
Switch among PU operation, external operation, and
NET operation while keeping the same operating status.
PU operation mode
External operation mode
NET operation mode
7
External operation mode (PU operation interlock)
X12 signal ON
*2
Operation mode can be switched to PU operation
mode.
(output stop during external operation)
X12 signal OFF
*2
Operation mode can not be switched to the PU
operation mode.