Parameter List
Remote output
function
(REM signal)
495
Remote output selection
10
0
Remote output data clear
at power OFF
Remote output data is
cleared during an
inverter reset
1
Remote output data
retention at power OFF
10
Remote output data clear
at power OFF
Remote output data is
retained during an
inverter reset
11
Remote output data
retention at power OFF
496
Remote output data 1
1 0 0 to 4095
Output terminal can be switched on and off.
497
Remote output data 2
1 0 0 to 4095
Maintenance of parts
503
Maintenance timer
10
0 (1 to 9998)
Displays the cumulative energization time of the
inverter in 100h increments.
Reading only
Writing the setting of "0" clears the cumulative
energization time.
504
Maintenance timer alarm
output set time
1 9999
0 to 9998
Set the time taken until when the maintenance timer
alarm output signal (Y95) is output.
9999 No function
505
Refer to Pr. 37.
516 to 519
Refer to Pr. 29.
539
Refer to Pr. 343.
Inverter setup using
USB communication
547
USB communication station
number
1 0 0 to 31 Specify the inverter station number.
548
USB communication check
time interval
0.1s 9999
0
USB communication is enabled. However, the
inverter will come to an alarm stop (E. USB) if
operation is changed to PU operation mode.
0.1 to 999.8s
Set the interval of communication check time.
9999 No communication check
551
Refer to
Pr. 338
and Pr. 339
.
549 to 551
Refer to Pr. 343.
Current average value
monitor signal
555
Current average time
0.1s 1s 0.1 to 1.0s
Set the time taken to average the current during start
bit output (1s).
556
Data output mask time
0.1s 0s 0.0 to 20.0s
Set the time for not obtaining (mask) transient state
data.
557
Current average value
monitor signal output
reference current
0.01A
Rated
inverter
current
0 to 500A
Set the reference (100%) for outputting the signal of
the current average value.
563, 564
Refer to Pr. 52.
569
Refer to Pr. 80.
571
Refer to Pr. 13.
574
Refer to Pr. 95.
575 to 577
Refer to Pr. 127.
611
Refer to Pr. 57.
665
Refer to Pr. 882.
684
Refer to Pr. 82.
800
Refer to Pr. 81.
802
Refer to Pr. 10.
803
Refer to Pr. 22.