(1) Before performing offline auto tuning
Check the following before performing offline auto tuning.
· Make sure Advanced magnetic flux vector control (Pr. 80, Pr. 81), Real sensorless vector control or vector control
(Pr. 800) is selected. (Refer to page 63 )
· A motor should be connected. Note that the motor should be at a stop at a tuning start.
· The motor capacity should be equal to or one rank lower than the inverter capacity.
· Motors such as high-slip motor, high-speed motor and special motor cannot be tuned. (The maximum frequency is
120Hz.)
· Even if tuning is performed without motor running (Pr. 96 Auto tuning setting/status = "1"), the motor may run slightly.
Therefore, fix the motor securely with a mechanical brake, or before tuning, make sure that there will be no
problem in safety if the motor runs. (Caution is required especially in vertical lift applications). Note that if the motor
runs slightly, tuning performance is unaffected.
· Note the following when selecting offline auto tuning performed with motor running (Pr. 96 Auto tuning setting/status =
"101").
Torque is not enough during tuning.
The motor may be run at nearly its rated speed.
The mechanical brake is open.
No external force is applied to rotate the motor.
· Offline auto tuning will not be performed properly if it is performed with a surge voltage suppression filter (FR-ASF-
H) connected between the inverter and motor. Remove it before starting tuning.
· When exercising vector control, use the encoder that is coupled directly to the motor shaft without looseness.
Speed ratio should be 1:1.