Parameter List
Condition selection of
function validity by the second
function selection signal
(RT) and third function(X9)
155
RT signal function validity
condition selection
10
0
Second (third) function is immediately valid with on of
the RT (X9) signal.
10
Second (third) function is valid only during the RT
(X9) signal is on and constant speed operation.
(invalid during acceleration/deceleration)
156, 157
Refer to Pr. 22 .
158
Refer to Pr. 54 .
159
Refer to Pr. 135 .
User group function
160
User group read selection
10
0 All parameters can be displayed.
1
Only the parameters registered in the user group can
be displayed.
9999 Only the simple mode parameters can be displayed.
172
User group registered
display/batch clear
10
(0 to 16)
Displays the number of cases registered as a user
group (reading only).
9999 Batch clear the user group registration
173
User group registration
1 9999
0 to 999,
9999
Set the parameter numbers to be registered to the
user group.
Read value is always "9999".
174
User group clear
1 9999
0 to 999,
9999
Set the parameter numbers to be cleared from the
user group.
Read value is always "9999".
Operation selection
of the operation panel
161
Frequency setting/key lock
operation selection
10
0
Setting dial frequency
setting mode
Key lock invalid
1
Setting dial potentiometer
mode
10
Setting dial frequency
setting mode
Key lock valid
11
Setting dial potentiometer
mode
162 to 165
Refer to Pr. 57.
166, 167
Refer to Pr. 150.
168, 169
Parameter for manufacturer setting. Do not set.
170, 171
Refer to Pr. 52.
172 to 174
Refer to Pr. 160.
Func
t
ion
Parameter
Name
Incre
ments
Initial
Value
Range Description
Related
parameters