114
Parameter List
Analog input selection
73
Analog input selection
11
0 to 7,
10 to 17
You can select the input specifications of terminal 2
(0 to 5V, 0 to 10V, 0 to 20mA) and input specifications
of terminal 1 (0 to ±5V, 0 to ±10V).
To change the terminal 2 to the voltage input
specification (0 to 5V/ 0 to 10V), turn OFF (initial
status) the voltage/current input switch 2. To change
it to the current input (0 to 20mA), turn ON the
voltage/current input switch 2.
Override and reversible operation can be selected.
242
Terminal 1 added
compensation amount
(terminal 2)
0.1% 100% 0 to 100%
Set the ratio of added compensation amount when
terminal 2 is the main speed.
243
Terminal 1 added
compensation amount
(terminal 4)
0.1% 75% 0 to 100%
Set the ratio of added compensation amount when
terminal 4 is the main speed.
252
Override bias
0.1% 50% 0 to 200%
Set the bias side compensation value of override
function.
253
Override gain
0.1% 150% 0 to 200%
Set the gain side compensation value of override
function.
267
Terminal 4 input selection
10
0
Terminal 4 input
4 to 20mA
Turn ON the voltage/
current input switch
1(initial status).
1
Terminal 4 input
0 to 5V
Turn OFF the voltage/
current input switch 1.
2
Terminal 4 input
0 to 10V
Response level of analog input
and noise elimination
74
Input filter time constant
11 0 to 8
The primary delay filter time constant for the analog
input can be set.
A larger setting results slower response.
822
Speed setting filter 1
0.001s 9999
0 to 5s,
9999
Set the time constant of the primary delay filter
relative to the external speed command (analog input
command).
826
Torque setting filter 1
0.001s 9999
0 to 5s,
9999
Set the time constant of the primary delay filter
relative to the external torque command (analog
input command).
832
Speed setting filter 2
0.001s 9999
0 to 5s,
9999
Second function of Pr. 822 (valid when the RT
terminal is on)
836
Torque setting filter 2
0.001s 9999
0 to 5s,
9999
Second function of Pr. 826 (valid when the RT
terminal is on)
849
Analog input offset
adjustment
0.1% 100% 0 to 200%
This function provides speed command by analog
input (terminal 2) with offset and avoids frequency
command to be given due to noise under 0 speed
command.
Reset selection,
disconnected PU
detection
75
Reset selection/
disconnected PU detection/
PU stop selection
114
0 to 3,
14 to 17
You can select the reset input acceptance, disconnected
PU (FR-DU07
/FR-PU07/FR-PU04) connector
detection function and PU stop function.
For the initial value, reset always enabled, without
disconnected PU detection, and with PU stop
function are set.
Output
function
of alarm code
76
Fault code output selection
10
0 Without fault code output
1 With fault code output
2 Fault code output at fault occurrence only
Prevention of
parameter
rewrite
77
Parameter write selection
10
0 Write is enabled only during a stop
1 Parameter write is disabled.
2
Parameter write is enabled in any operation mode
regardless of operating status.
Prevention of
reverse rotation
of the motor
78
Reverse rotation prevention
selection
10
0 Both forward and reverse rotations allowed
1 Reverse rotation disallowed
2 Forward rotation disallowed
Func
t
ion
Parameter
Name
Incre
ments
Initial
Value
Range Description
Related
parameters