Mitsubishi Electronics FR-E500 Marine Radio User Manual


 
PARAMETERS
91
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
(multi-speed operation)
Pr. 180 to Pr. 183
(input terminal (DeviceNet
input) function selection)
Related parameters
"
" Operation mode selection (Pr. 79)
4.2.26 Operation mode selection (Pr. 79)
Pr. 79 "operation mode selection"
Used to select the operation mode of the inverter.
The inverter can be run from the parameter unit
(PU operation) and DeviceNet signals (DeviceNet
operation).
When power is switched on (factory setting), the DeviceNet operation mode is
selected.
Parameter
Number
Factory
Setting
Setting
Range
79 2 0 to 2
<Setting>
In the following table, operation using the parameter unit is abbreviated to PU
operation.
Pr. 79
Setting
Function
0
When power is switched on, the DeviceNet operation mode is selected.
PU or DeviceNet operation can be selected by pressing the
PU
/
EXT
keys of the
parameter unit. For these modes, refer to the setting 1 and 2 below.
Operation mode Running frequency Start signal
1
PU operation
mode (PU)
Di
g
ital settin
g
b
y
the ke
y
operation of parameter unit
FWD
or
REV
key of parameter
unit
2
DeviceNet
operation mode
(NET)
DeviceNet master unit