3.3.3 Input from DeviceNet to inverter
Control input commands
The FR-E500KND supports STF and STR. Some other Control Input Commands are
supported as well.
Output Frequency Setting
Output frequency setting is possible for the range 0 to 400 Hz in increments of 0.01 Hz.
Inverter reset
The inverter can be reset via DeviceNet using the ldentity Object reset service.
Note that this reset service also performs a parameter clear, the type of which depends
upon the type of the ldentity Object reset service. (Refer to page 157.)
Parameter writing
Refer to page 173 for parameters.
3.3.4 Output from inverter to DeviceNet
Inverter status
The inverter status can be monitored using class 0x2A, attribute 114, the FR-E500KND
inverter status. This is a bitmapped status byte defined as follows:
Bit Definition
0 Running (RUN)
1 Forward running (FWD)
2 Reverse running (REV)
3 Up to frequency (SU)
4 Overload (OL)
5—
6 Frequency detection (FU)
7Alarm
Inverter monitoring
!
Output frequency
!
Output current
!
Output voltage
Parameter read
Refer to page 173 for parameters.
Some inverter parameters require configuration to be viewed via the PU. All supported
parameters are fully accessible regardless of inverter configuration in such cases.