PARAMETERS
70
"
Starting frequency (Pr. 13)
4.2.8 Starting frequency (Pr. 13)
Pr. 13 "starting frequency"
You can set the starting frequency between 0 and 60Hz.
!
Set the starting frequency at which the start signal is switched on.
Parameter
Number
Factory
Setting
Setting
Range
13 0.5Hz 0 to 60Hz
Note: The inverter will not start if the frequency setting signal is less than the value
set in Pr. 13 "starting frequency".
For example, when 5Hz is set in Pr. 13, the motor will not start running until
the frequency setting signal reaches 5Hz.
CAUTION
When the Pr. 13 setting is equal to or less than the Pr. 2 value, note that
merely switching on the start signal will start the motor at the preset
frequency if the command frequency is not input.
Time
60
Pr.13
ON
0
Output frequency
(Hz)
Foward rotation
Frequency setting signal(V)
Setting range
Pr. 2 "minimum frequency"
Related parameters