Mitsubishi Electronics FR-E500 Marine Radio User Manual


 
PARAMETERS
57
Func-
tion
Param-
eter
Number
Name
Setting
Range
Minimum
Setting
Increments
Factory
Setting
Refer
To:
Custo-
mer
Setting
71 Applied motor (Note 4)
0, 1, 3, 5, 6,
13, 15, 16,
23, 100, 101,
103, 105,
106, 113,
115, 116,
123,
1086
72 PWM frequency selection 0 to 15 1 1 87
75
Reset selection/
disconnected PU detection/
PU stop selection
0 to 3,
14 to 17
11488
77
Parameter write disable
selection
0, 2 1 0 90
78
Reverse rotation prevention
selection
0, 1, 2 1 0 90
Operation selection functions
79
Operation mode selection
(Note 4)
0, 1, 2 1 2 91
80 Motor capacity (Note 4)
0.1 to
7.5kW, 9999
0.01kW 9999 92
82 Motor exciting current
0 to 500A,
9999
0.01A 9999 93
83
Rated motor voltage
(Note 4)
0 to 1000V 0.1V 200V 93
84
Rated motor frequency
(Note 4)
50 to 120Hz 0.01Hz 60Hz 93
90 Motor constant (R1)
0 to 50
,
9999
0.001
9999 93
Motor constants
96
Auto-tuning setting/status
(Note 4)
0, 1 1 0 93
117 Station number 0 to 31 1 0 99
118 Communication speed 48, 96, 192 1 192 99
119 Stop bit length
0, 1
(data length 8)
10, 11
(data length 7)
1199
120
Parity check
presence/absence
0, 1, 2 1 2 99
121
Number of communication
retries
0 to 10,9999 1 1 99
122
Communication check time
interval
0, 0.1 to
999.8 s,
9999
0.1 s 0 99
123 Waiting time setting
0 to 150,
9999
1 9999 99
Communication functions
124
CR
LF presence/absence
selection
0, 1, 2 1 1 99
Display
145
Parameter unit display
language selection
0 to 7 1 0 112
150
Output current detection
level
0 to 200% 0.1% 150% 113
151
Output current detection
period
0 to 10 s 0.1 s 0 113
152 Zero current detection level 0 to 200.0% 0.1% 5.0% 114
Current detection
153
Zero current detection
period
0.05 to 1 s 0.01 s 0.5 s 114
Parameter List