" Stall prevention (Pr. 22, Pr. 23, Pr. 66)
4.2.10 Stall prevention (Pr. 22, Pr. 23, Pr. 66)
Pr. 22 "stall prevention operation level"
Pr. 23 "stall prevention operation level
compensation factor at double
speed"
Pr. 66 "stall prevention operation level reduction starting frequency"
!
Set the output current level at which the output frequency will be adjusted to prevent
the inverter from stopping due to overcurrent etc.
!
For high-speed operation at or over the motor base frequency, acceleration may not
be made because the motor current does not increase.
To improve the operation characteristics of the motor in such a case, the stall
prevention level in the high-frequency range can be reduced. This is effective for
operation of a centrifugal separator up to the high-speed range. Normally, set 60Hz
in Pr. 66 and 100% in Pr. 23.
!
For operation in the high-frequency range, the current in the locked motor state is
smaller than the rated output current of the inverter and the inverter does not result
in an alarm (protective function is not activated) if the motor is at a stop. To improve
this and activate the alarm, the stall prevention level can be reduced.
Parameter
Number
Factory
Setting
Setting
Range
Remarks
22 150% 0 to 200%
23 9999
0 to 200%,
9999
9999: Constant
according to Pr. 22
66 60Hz 0 to 400Hz
Pr.22
Pr.23
Pr.23
=9999
400Hz
Pr.66
Reduction ratio
compensation factor (%)
Stall prevention
operation level (%)
Output frequency (Hz)
150
90
60
45
30
22.5
600 100 200 300 400
Setting example
(Pr.22=150%, Pr.23=100%, Pr.66=60Hz)
Current limit
operation level (%)
Output frequency (Hz)
Pr. 9 "electronic thermal O/L
relay"
Pr. 48 "second electronic
overcurrent protection"
Related parameters