PARAMETERS
117
"
User group selection (Pr. 160, Pr. 173 to Pr. 176)
4.2.34 User group selection (Pr. 160, Pr. 173 to Pr. 176)
Pr. 160 "user group read selection"
Pr. 173 "user group 1 registration"
Pr. 174 "user group 1 deletion"
Pr. 175 "user group 2 registration"
Pr. 176 "user group 2 deletion"
Among all parameters, a total of 32 parameters can be registered to two different user
groups. The registered parameters may only be accessed.
The other parameters cannot be read.
Parameter
Number
Factory
Setting
Setting Range Remarks
160 0 0, 1, 10, 11
173 0 0 to 999
174 0 0 to 999, 9999 9999: Batch deletion
175 0 0 to 999
176 0 0 to 999, 9999 9999: Batch deletion
<Examples of use>
(1) Registration of parameter to user group
Write the parameter numbers to be registered to Pr. 173 (User group 1 registration) or
Pr. 175 (User group 2 registration). Write the parameter numbers one by one.
(2) Deletion of parameter from the user group
Write the parameter numbers to be deleted to Pr. 174 (User group 1 deletion) or
Pr. 176 (User group 2 deletion). Write the parameter numbers one by one.
(3) Set the required value in Pr. 160 to make the user group or groups
valid or invalid.
Pr. 160 Setting Description
0 Previous parameters read
1 User group 1's parameters read
10 User group 2's parameters read
11 User group 1 and 2 parameters read
Note:1. The Pr. 77, Pr. 160 and Pr. 991 values may always be read independently of
the user group setting.
2. The Pr. 173 or Pr. 174 value read indicates the number of parameters
registered to group 1, and the Pr. 175 or Pr. 176 value read indicates the
number of parameters registered to group 2.
3. If "0" is set in the second digit of two-digit Pr. 160, it is not displayed.
However, "0" is displayed when it is set in the first digit only.
4. When "9999" is set in Pr. 174 or Pr. 176, the parameters registered to the
corresponding user group are batch-deleted.