PARAMETERS
78
"
" Frequency at 5V (10V) input (Pr. 38)
"
" Up-to-frequency sensitivity (Pr. 41)
4.2.15 Up-to-frequency sensitivity (Pr. 41)
Pr. 41 "up-to-frequency sensitivity"
The ON range of the up-to-frequency signal (SU) output when the output frequency
reaches the running frequency can be adjusted between 0 and
±
100% of the running
frequency.
This parameter can be used to ensure that the running frequency has been reached or
used as the operation start signal etc. for related equipment.
Parameter
Number
Factory
Setting
Setting
Range
41 10% 0 to 100%
Output signal
SU
ON
Pr.41
Time
OFFOFF
Adjustable range
Running frequency
Output frequency (Hz)
!
Use Pr. 192 to allocate the terminal used for SU signal output.
Refer to page 120 for Pr. 192 "A, B, C terminal (ABC) function selection".
!
The DeviceNet output is the 3-bit inverter status.
Note: When terminal assignment is changed using Pr. 192, the other functions may
be affected. Check the functions of the corresponding terminals before
making settings.
4.2.16 Output frequency detection (Pr. 42, Pr. 43)
"
Output frequency detection (Pr. 42, Pr. 43)
Pr. 42 "output frequency detection"
Pr. 43 "output frequency detection
for reverse rotation"
The output frequency detection signal (FU) is output when the output frequency
reaches or exceeds the setting. This function can be used for electromagnetic brake
operation, open signal etc.
!
You can also set the detection of the frequency used exclusively for reverse rotation.
This function is effective for switching the timing of electromagnetic brake operation
between forward rotation (rise) and reverse rotation (fall) during vertical lift operation
etc.
Parameter
Number
Factory
Setting
Setting Range Remarks
42 6Hz 0 to 400Hz
43 9999 0 to 400Hz, 9999 9999: Same as Pr. 42 setting
Pr. 192 "A, B, C terminal (ABC)
function selection"
Related parameters
Pr. 192 "A, B, C terminal (ABC)
function selection"
Related parameters
4