178
Definition of each registration
Name Description Definition
Default
Setting
Watch dog
timeout
operation (WDA)
(Note)
DeviceNet connection object
(Class code 0x05) instance 2
attribute 12
0 = Shift to timeout
1 = Automatic deletion
2 = Automatic reset
0
DN fault mode
Supports control management
object (Class code 0x29)
instance attribute 16, DN fault
mode
0 = Fault + stop
1 = Ignore
0
Input assembly
Assemble ID value used for
connection object. (Class code
0x05) instance attribute 16,
consumed_connection_path
Assemble instance ID
0 = 0x46 (70) 4byteMode
1 = 0x47 (71) 4byteMode
6 = 0xB0 (176) 6byteMode
8 = 0x96 (150) 8byteMode
1
Output
assembly
Assemble ID value used for
connection object. (Class code
0x05) instance attribute 14,
produced_connection_ path
Assemble instance ID
0 = 0x14 (20) 4byteMode
1 = 0x15 (21) 4byteMode
6 = 0x7E (126) 6byteMode
8 = 0x64 (100) 8byteMode
1
Baud rate
DeviceNet object value (Class
code 0x03 instance attribute 2,
baud rate
0 = 125kbps
1 = 250kbps
2 = 500kbps
0
Device address
DeviceNet object value (Class
code 0x03 instance attribute 1,
MAC ID
Node address: range is 0 to 63
(Same as attribute definition)
63
Address key Internal confirmation
1010 - preset; No other
definitions
1010
Baud rate Internal confirmation
0101 - preset; No other
definitions
0101
Note: The parameter setting will be changed back to the factory setting (0) when
reconnected after a disconnection.
(4) Class 0x67 Instance Services
Service Code Service
0x0E Get Attribute Single
0x10 Set Attribute Single