(7) Class 0x04 - Input Instance 150
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
−−
OL FU
Faulted
Running
Rev
Running
Fwd
10x00
2 Actual Speed (Low Byte)
3 Actual Speed (High Byte)
4 Output Current (Low Byte)
5 Output Current (High Byte)
6 Error Factor
Instance
0x96
150
70x00
Data Name Contents
OL 1 is set during stall prevention operation.
FU 1 is set when output frequency reaches or exceeds the setting.
Faulted 1 is set when an inverter trip occurs.
Running Rev If Running Rev = 1, running in reverse direction.
Running Fwd If Running = 1, running in forward direction.
Actual Speed
Byte 2: Low-order byte of actual speed.
Byte 3: High-order byte of actual speed.
Output Current
Byte 4: Low-order byte of output current.
Byte 5: High-order byte of output current.
Error Factor Error factor code when inverter alarm occurs.
Note: Output instance (100)
If any of the requests to the inverter of MRS, Fault Reset, Run Rev, Run
Fwd, speed setting, acceleration time or deceleration time fail, this
instance response will be an error response.
Limitation (MRS)
The MRS terminal can be assigned with Pr. 183.
When using the MRS terminal Pr. 183 must be assigned to “6”.