PARAMETERS
125
4.2.42 DeviceNet specific parameters (Pr. 345 to Pr. 348)
Pr. 345 "DeviceNet Address Startup Data (Lower byte)"
Pr. 346 "DeviceNet Baudrate Startup Data (Lower byte)"
Pr. 347 "DeviceNet Address Startup (Higher byte)"
Pr. 348 "DeviceNet Baudrate Startup Data (Higher byte)"
Pr. 345 to Pr. 348 are specific DeviceNet parameters. They are described below.
Pr. No. Function
Setting
Range
Minimum
Increment
Default
Setting
345
DeviceNet Address
Startup Data (Lower byte)
0 to 255 1 63 (0x3F)
346
DeviceNet Baudrate
Startup Data (Lower byte)
0 to 255 1 132 (0x84)
347
DeviceNet Address
Startup Data (Higher byte)
0 to 255 1 160 (0xA0)
348
DeviceNet Baudrate
Startup Data (Higher byte)
0 to 255 1 80 (0x50)
The PU displays only in decimal integers. The hexadecimal integers in the parentheses
are used here for easy bitmap reference only.
Pr. 345 and Pr. 347 are bit-mapped parameters and are defined as follows.
14 1315 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit7654321Bit0 Bit7 6 5 4 3 2 1 Bit0
WDA
Pr.347 Pr.345
Address key
DN fault mode Device node address
Pr. 346 and Pr. 348 are bit-mapped parameters and are defined as follows.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit7654321Bit0 Bit7 6 5 4 3 2 1 Bit0
Pr.348 Pr.346
Baud rate key Input assembly Output assembly Baud rate