Mitsubishi Electronics FR-V520-1.5K to 55K Marine Battery User Manual


 
111
Operation selection function 2 (Pr. 65 to Pr. 79)
PARAMETERS
3
3.11.2 Applied motor (Pr. 71, Pr. 450 )
Set the motor used.
When using an other manufacturer’s motor, set "3" or "13" in Pr.71 and perform offline auto tuning. Refer to the
Instruction Manual (basic) for the motor setting, etc.
<Setting>
Refer to the following table and set this parameter according to the motor used.
Parameter Name Factory Setting Setting Range Remarks
71 Applied motor 30
0, 3 to 8, 10, 13 to 18,
20, 23, 24, 30, 33, 34
450 Second applied motor 9999 0, 10, 30, 9999
9999: Second applied
motor invalid
Setting
Motor Control Constants
0 Mitsubishi standard motor (SF-JR) Inverter internal constants
3
Other manufacturer’s standard motor
Offline auto tuning
4 Offline auto tuning data utilization
5 Star connection direct input
6 Delta connection direct input
7 Star connection direct input + offline auto tuning
8 Delta connection direct input + offline auto tuning
10
Mitsubishi constant-torque motor
(SF-HRCA)
Inverter internal constants
13
Other manufacturer’s constant-torque
motor
Offline auto tuning
14 Offline auto tuning data utilization
15 Star connection direct input
16 Delta connection direct input
17 Star connection direct input + offline auto tuning
18 Delta connection direct input + offline auto tuning
20
SF-JR (4P)-1.5kW or less
(during vector control)
Inverter internal constants
23 Offline auto tuning
24 Offline auto tuning data utilization
30
(factory setting)
SF-V5RU dedicated motor
(including SF-VR type motor)
Inverter internal constants
33 Offline auto tuning
34 Offline auto tuning data utilization
CAUTION
1. Refer to page 120 for offline auto tuning.
2. Refer to page 39 for details of setting conventional Mitsubishi motors and other manufacturer’s
motors.
CAUTION
Set this parameter correctly according to the motor used.
REMARKS
For online auto tuning, refer to the Instruction Manual (basic).
speed torque position