Mitsubishi Electronics FR-V520-1.5K to 55K Marine Battery User Manual


 
115
Operation selection function 2 (Pr. 65 to Pr. 79)
PARAMETERS
3
3.11.5 Reset selection/disconnected PU detection/PU stop selection
(Pr. 75 )
<Setting>
(1) Restarting method when stop was made by inputting from the control panel
(Method of restarting from indication)
1)After the motor has decelerated to a stop, turn off the STF or STR signal.
2)Press twice* to display .
(*For monitor screen)
....... Refer to the Instruction Manual (basic) for details of the monitor display provided
by pressing .
3)Press .
4)Turn on the STF or STR signal.
You can select the reset input acceptance, PU (FR-DU04-
1/FR-PU04V) connector disconnection detection
function and PU stop function.
z Reset selection: You can select the reset function input (RES signal) timing.
z Disconnected PU detection: When the disconnection of the PU (FR-DU04-1/FR-PU04V) from the inverter for
more than 1s is detected, the inverter outputs an alarm code (E.PUE) and
comes to an alarm stop.
The motor decelerates to a stop when the PU is disconnected during PU jog
operation with Pr. 75 set to any of "0, 1, 14, 15"(operation is continued if the PU
is disconnected).
z PU stop selection: When an alarm etc. occurs in any operation mode, you can stop the motor from
the control panel by pressing .
Parameter Name
Factory
Setting
Setting Range Remarks
75
Reset selection/disconnected PU
detection/PU stop selection
14 0 to 3, 14 to 17 Extended mode
Pr. 75
Setting
Reset Selection
Disconnected PU
Detection
PU Stop Selection
0 Reset input is always enabled.
If the PU is disconnected,
operation will be continued
as-is.
The PU stop key is invalid.
input is valid only in the PU or combined
operation mode (Pr. 79 = "4").
1
Reset input is enabled only when the
protective function is activated.
2 Reset input is always enabled.
When the PU is
disconnected, the inverter
output is shut off.
3
Reset input is enabled only when the
protective function is activated.
14 Reset input is always enabled.
If the PU is disconnected,
operation will be continued
as-is.
input decelerates the motor
to a stop in any of the PU, external and
communication operation modes.
15
Reset input is enabled only when the
protective function is activated.
16 Reset input is always enabled.
When the PU is
disconnected, the inverter
output is shut off.
17
Reset input is enabled only when the
protective function is activated.
CAUTION
When Pr. 79 = "3", press three times to display . Then press and proceed to 3).
REMARKS
If the reset signal (RES) is provided during operation, the inverter shuts off its output while it is reset, the internal thermal
integrated value of the electronic thermal relay function and the number of retries are reset, and the motor coasts.
The Pr. 75 value can be set any time. This value does not return to the initial value even if parameter (all) clear is executed.
When the motor is stopped from the PU, and are displayed alternately. An alarm output is not provided.
speed torque position
STOP
RESET
STOP
RESET
STOP
RESET
STOP
RESET
MODE
MODE
MODE
SET