Mitsubishi Electronics FR-V520-1.5K to 55K Marine Battery User Manual


 
196
Model specifications
4.1 Model specifications
z 200V class (for use with the Mitsubishi dedicated motor [SF-V5RU (1500r/min series)])
Inverter
Type FR-V520-[][]K 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55
Applied motor capacity (kW) 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55
Output
Rated capacity (kVA)
(Caution 1)
3.1 4.5 6.9 9.8 13.0 18.7 25.2 30.4 35.8 43.8 58.1 68.5 91.0
Rated current (A) 9.0 13.0 20.0 28.5 37.5 54 72.8 88 103.5 126.5 168 198 264
Overload current rating
(Caution 2)
150% 60s, 200% 0.5s (inverse-time characteristics)
Regenerative
braking
torque
Max. value/
permissible
duty
100% torque/3%ED
(Caution 3)
(Caution 7)
100%
torque/
2%ED
(Caution
3)
(Caution
7
)
20% torque/continuous (Caution 7)
Power supply
Rated input AC voltage,
frequency
Three-phase, 200V to 220V 50Hz, 200 to 240V 60Hz
Three-phase, 200 to 220V 50Hz, 200 to 230V 60Hz
Permissible AC voltage
fluctuation
170 to 242V 50Hz, 170 to 264V 60Hz 170 to 242V 50Hz, 170 to 253V 60Hz
Permissible frequency
fluctuation
±5%
Instantaneous voltage
drop immunity
Operation continues at 165V or higher voltage. If the rated voltage drops to lower than 165V, 15ms operation continues.
Power supply capacity
(kVA) (Caution 4)
5.0 6.5 10 14 19 23 33 39 48 57 77 90 123
Protective structure (JEM
1030)
Enclosed type (IP20) (Caution 5) Open type (IP00)
Cooling system Forced air cooling
Approx. mass (kg) 3.5 3.5 6.0 6.0 6.0 14.0 14.0 21.0 30.0 40.0 40.0 55.0 58.0
Dedicated motor
Motor type (Caution 8)
SF-V5RU
1K
SF-V5RU
2K
SF-V5RU
3K
SF-V5RU
5K
SF-V5RU
7K
SF-V5RU
11K
SF-V5RU
15K
SF-V5RU
18K
SF-V5RU
22K
SF-V5RU
30K
SF-V5RU
37K
SF-V5RU
45K
SF-V5RU
55K
Rated output (kW) 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55
Rated torque (Nm) 9.55 14.1 23.6 35.0 47.7 70.0 95.5 118 140 191 235 286 350
Maximum torque 150% 60s
(Nm)
14.3 21.1 35.4 52.4 71.6 105 143 176 211 287 353 429 525
Rated speed (r/min) 1500
Maximum speed (r/min)
3000 (Caution 6) 2400
Frame No. 90L 100L 112M 132S 132M 160M 160L 180M 180M 200L 200L 200L 225S
Moment of inertia J
(X10
-4
kgm
2
)
67.5 105 175 275 400 750 875 1725 1875 3250 3625 3625 6850
Noise (Caution 11) 75dB or less 80dB or less
85dB
or less
Cooling fan
(with thermal
protector)
Voltage
Single-phase 200V/50Hz
Single-phase 200 to 230V/60Hz
Three-phase 200V/50Hz
Three-phase 200 to 230V/60Hz
Input
(50Hz/60Hz)
(Caution 9)
36/55W
(0.26/0.32A)
22/28W
(0.11/0.13A)
55/71W
(0.37/0.39A)
100/156W
(0.47/0.53A)
85/
130W
(0.46/
0.52A)
Ambient temperature,
humidity
-10 to +40°C (non-freezing), 90%RH or less (non-condensing)
Structure
(Protective structure)
Totally enclosed forced draft system (Motor: IP44, cooling fan: IP23S) (Caution 10)
Detector Encoder 2048P/R, A phase, B phase, Z phase +12VDC power supply
Equipment Encoder, thermal relay protector, fan
Heat resistance class
F
Vibration rank V10
Approx. weight (kg) 24 33 41 52 62 99 113 138 160 238 255 255 320
Dedicated
Encoder cable
Resolution
2048 pulse/rev
Power supply voltage 12VDC±10%
Current consumption 90mA
Output signal form A, B phases (90° phase shift) Z phase: 1 pulse/rev
Output circuit Complimentary (constant voltage output matched by emitter follow)
Output voltage "H" level: Power supply voltage 9V or more (IOH: -20mA), "L" level: Power supply voltage 3V or less (IOL: 20mA)
CAUTION
1. The rated output capacity indicated assumes that the output voltage is 200V.
2. The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output
current. For repeated duty, allow time for the inverter and motor to return to or below the temperatures under 100% load.
3. The short-time rating is 5s.
4. The power supply capacity varies with the value of the power supply side inverter impedance (including those of
the input reactor and cables).
5. Open type (IP00) when the plug-in option is fitted after removal of the option wiring port cover.
6. You can run the 3.7kW or less dedicated motor at the maximum speed of 3600r/min, consult us when you want to
run the motor at higher than 3000r/min.
7. With the dedicated external brake resistor FR-ABR (option), the 1.5K to 7.5K and 11K to 15K will achieve the
performance of 100% torque/10%ED and 100% torque/6%ED respectively.
8. If the motor is one rank lower in capacity than the inverter, it can be used by setting Pr. 80 "motor capacity" and
Pr.
81 "number of motor poles". Other manufacturers’ motors and special motors can be used by performing online auto tuning.
9. Power (current) at 50Hz/60Hz.
10. Since a motor with brake has a window for gap check, the protective structure of both the cooling fan section and
brake section is IP20. S of IP23S is an additional code indicating the condition that protection from water intrusion
is established only when a cooling fan is not operating.
11. The value when high carrier frequency is set (Pr. 72 = 6, Pr. 240 = 0).