Mitsubishi Electronics FR-V520-1.5K to 55K Marine Battery User Manual


 
159
Orientation (Pr. 350 to Pr. 362, Pr. 393 to Pr. 399)
PARAMETERS
3
3.27 Orientation (Pr. 350 to Pr. 362, Pr. 393 to Pr. 399)
3.27.1 Orientation control (Pr. 350, Pr. 351, Pr. 356, Pr. 357, Pr. 360 to Pr. 362, Pr. 393,
Pr. 396 to Pr. 399 )
<Settings>
If the orientation command signal (X22) is turned on during operation after the various parameters have been set,
the speed will decelerate to the "orientation switchover speed". After the "orientation stop distance" is calculated,
the speed will further decelerate, and the "orientation state" (servo lock) will be entered. The "orientation complete
signal" (ORA) will be output when the "orientation complete width" is entered.
(1) Setting I/O singals
Orientation is a function that stops a motor shaft at a position set by parameter using the motor built-in
position detector (encoder). Install the option (FR-V5AM or FR-A5AP) on the inverter to perform stop position
command control with a position detector (encoder) fitted to the machine. Refer to the instruction mannual of
the option for details.
Pr. 350 "stop position command selection" is factory-set to "9999" to make the orientation control function
invalid.
Parameter No. Name Setting Range Factory Setting Remarks
350 Stop position command selection 0, 1, 2, 3, 9999 9999
Extended mode
351 Orientation switchover speed 0 to 1000r/min 200r/min
356 Internal stop position command 0 to 16383 0
357 Orientation in-position zone 0 to 8192 11
360
External position command
selection
0, 1, 2 to 127 0
361 Position shift 0 to 16383 0
362 Orientation position loop gain 0.1 to 100 10
393 Orientation selection 1, 2, 10, 11, 12 0
396 Orientation speed gain (P term) 0 to 1000% 60%
397 Orientation speed integral time 0 to 20.0s 0.333s
398 Orientation speed gain (D term) 0 to 100.0% 1%
399 Orientation deceleration ratio 0 to 1000 20
REMARKS
Check the Pr. 851 and Pr. 852 settings. (Refer to the Insruction Manual (basic).)
Input Orientation command X22 signal
Orientation control is valid with the signal on.
Set "22" in any of Pr. 180 to Pr.183 or Pr. 187 (input
terminal function selection). (Refer to page 150.)
Output Orientaiton complete signal ORA signal
Switched low if the orientation has stopped within the
in-position zone while the start and orientation signals
are input.
Open collector output
Permissible load 24VDC, 0.1A
Set 27 in any of Pr.190 to Pr. 192 or Pr. 195 (output
terminal function selection).
(Refer to page 152.)
speed