Mitsubishi Electronics FR-V520-1.5K to 55K Marine Battery User Manual


 
172
Operation selection functions 4 (Pr. 800 to Pr. 809)
(3) Setting from the CC-Link (16bit two’s complement)
(1) Terminal 3 calibration (Pr. 804 = 0)
The torque command value for the analog input of
the terminal 3 varies with Pr. 904 and Pr. 905 as
shown on the right.
(2) Digital input from parameter (Pr. 804 = 1)
Digital setting of the torque command can be made
by writing the torque command value to Pr. 805 or
Pr. 806 by communication. The torque command
can also be specified by parameter direct setting.
In this case, set the speed limit value to an
appropriate value to prevent overspeed.
The relationship between the Pr. 805 or Pr. 806
setting and actual torque command value at this
time is shown on the right. On the assumption that
1000% is 0%, the torque command is indicated by
an offset from 1000%.
CAUTION
When writing the torque command value by communication (Pr. 804 = 1, Pr. 804 = 3), there is a limit on
the number of write times to E
2
PROM. When the value is changed often, write it to RAM. (When Pr. 804 =
1, set "1" in Pr. 342 "E
2
PROM write selection" to select write to RAM.)
Torque
command
-327.68% -100% -50% -25% 0% 25% 50% 100% 327.67%
-32768 -10000 -5000 -2500 0000 2500 5000 10000 32767
Hexadecimal 8000H D8F0H EC78H F63CH 0 09C4H 1388H 2710H 7FFFH
Decimal 32768 55536 60536 63036 0 2500 5000 10000 32767
CAUTION
The internal resolution of the torque command is 0.024% (100/2
12
) and the fraction less than the
resolution is rounded off.
The range of torque setting is from -327.68% to 327.67%. (-400% to 400% when shipped from the
factory)
A negative value can not be input from the control panel DU04-1 and parameter unit PU04V, a value can
not be set in 0.01% increments. The setting range is from 600 to 1400% and setting increments is 1%
increments. When the value set from the CC-Link is read from the PU04V or DU04-1, the value is also
converted to 600 to 1400 for display.
Torque command value
Terminal 3 input
Pr.905
Gain setting
Pr.904
Bias setting
Pr.904
Bias input
Pr.905
Gain input
Torque command value
400%
600%
1000% 1400%
-400%
Pr. 805 or Pr. 806 setting
Torque command value
= Pr. 805 or Pr.806 - 1000%