Mitsubishi Electronics FR-V520-1.5K to 55K Marine Battery User Manual


 
35
How to use the output signals (assigned terminals
DO1 to DO3, ABC) (Pr. 190 to Pr. 192, Pr. 195)
WIRING
1
1.9 How to use the output signals (assigned terminals DO1 to DO3, ABC)
(Pr. 190 to Pr. 192, Pr. 195)
The output terminals DO1, DO2, DO3, ABC vary in functions with the Pr. 190 to Pr. 192 and Pr. 195 settings.
<Setting>
Refer to the following table for the settings of Pr. 190 to Pr. 192 and Pr. 195.
Parameter Name
Terminal
Symbol
Factory
Setting
Factory-Set
Terminal Function
Setting Range Remarks
190
DO1 terminal
function
selection
RUN 0 Inverter running
0 to 8, 10 to 16, 20, 25 to 27,
30 to 37, 39, 40 to 44, 96 to 99,
100 to 108, 110 to 116, 120,
125 to 127, 130 to 137, 139,
140 to 144, 196 to 199, 9999
Extended
mode
191
DO2 terminal
function
selection
SU 1 Up to speed
192
DO3 terminal
function
selection
IPF 2
Instantaneous power
failure, undervoltage
195
ABC terminal
function
selection
A, B, C 99 Alarm output
Setting
Signal
Name
Function Operation
Positive
logic
Negative
logic
0 100 RUN Inverter running
Output when the start command is input.
For V/F control, this signal is output during operation when the inverter output
speed rises to or above the starting speed.
During DC injection brake, 0 speed control or servo lock, this signal is not output.
1 101 SU Up to speed Refer to Pr. 41 "up-to-speed sensitivity" (page 95).
2102IPF
Instantaneous
power failure or
undervoltage
Output at occurrence of an instantaneous power failure or undervoltage.
3 103 OL Overload alarm
Output when torque or speed limit is activated.
For V/F control, this signal is output while the stall prevention function is activated.
4104FU
Output speed
detection
Refer to Pr. 42, Pr. 43 (speed detection) (page 95).
5105FU2
Second output
speed detection
Refer to Pr. 50 "second speed detection" (page 95).
6106FU3
Third output speed
detection
Refer to Pr. 116 "third speed detection" (page 95).
7107RBP
Regenerative brake
prealarm
Output when 85% of the regenerative brake duty set in Pr. 70 is reached.
8108THP
Electronic thermal
relay function
prealarm
Output when the electronic thermal relay function cumulative value reaches 85% of
the preset level.
10 110 PU PU operation mode Output when the PU operation mode is selected.
11 111 RY
Inverter operation
ready
Output when the inverter can be started by switching the start signal on or while it
is running.
12 112 Y12
Output current
detection
Refer to Pr. 150 and 151 (output current detection) (page 146).
13 113 Y13
Zero current
detection
Refer to Pr. 152 and 153 (zero current detection) (page 147).
14 114 FDN PID lower limit
Refer to Pr. 128 to 134 (PID control) (page 139).
15 115 FUP PID upper limit
16 116 RL
PID forward-reverse
rotation output
20 120 BOF
Brake opening
request
Refer to Pr. 278 to Pr. 285 (brake sequence function) (page 106).
25 125 FAN Fan fault output Output at the time of a fan fault.
26 126 FIN
Fin overheat
prealarm
Output when the heatsink temperature reaches about 85% of the heatsink
overheat protection activating temperature.
27 127 ORA
Orientation
in-position
When orientation is valid
30 130 Y30
Forward rotation
output
For vector control
31 131 Y31
Reverse rotation
output