Mitsubishi Electronics FR-V520-1.5K to 55K Marine Battery User Manual


 
118
Operation selection function 2 (Pr. 65 to Pr. 79)
<Setting>
In the following table, operation from the control panel or parameter unit is abbreviated to PU operation.
(1) Switchover mode
PU operation, external operation and computer link operation (when used with the communication option) can be
used by switching between them.
Pr. 79
Setting
Function
0
At power on, the external operation mode is selected. You can change between the PU operation mode and
external operation mode from the control panel ( ) or parameter unit ( / ). Refer to the fields of
settings 1 and 2 for the corresponding modes.
1
Operation mode Speed command Start signal
PU operation
mode
Setting from the control panel or FR-PU04V
,
2
External operation
mode
External signal input
(across terminals 2(1)-5, multi-speed selection, jog)
External signal input
(terminal STF, STR)
3
External/PU
combined
operation mode 1
Digital setting by PU key operation or external signal input
(multi-speed setting)
External signal input
(terminal STF, STR)
4
External/PU
combined
operation mode 2
External signal input (across terminals 2(1)-5, multi-speed
selection, jog)
,
6
Switchover mode
Switchover between PU operation, external operation and computer link operation (when a communication
option is used) can be done while running.
7
External operation mode (PU operation interlock)
X12 signal ON......Can be switched to PU operation mode
(output stop during external operation)
X12 signal OFF ....Switching to PU operation mode inhibited
8
Operation mode switchover using external signal (disallowed during operation)
X16 signal ON......Switched to external operation mode
X16 signal OFF ....Switched to PU operation mode
REMARKS
A stop function (PU stop selection) by of the PU (FR-DU04-1/FR-PU04V) is made valid during the operation
other than the PU operation mode. (Refer to page 115)
Either "3" or "4" may be set to select the PU/external combined operation, and these settings differ in starting method.
Refer to page 128 for the computer link operation mode.
Operation Mode Switching Switching Operation/Operating Status
External operation to PU operation
1) Change the operation mode to the PU operation mode from the control panel or
parameter unit.
• Rotation direction is the same as that of external operation.
• Set speed is as set by the potentiometer (speed setting potentiometer). (Note that
the setting will disappear when power is switched off or the inverter is reset.)
External operation to computer link
operation
1) Mode change command to computer link mode is transmitted from the computer.
• Rotation direction is the same as that of external operation.
• Set speed is as set by the potentiometer (speed setting potentiometer). (Note that
the setting will disappear when power is switched off or the inverter is reset.)
PU operation to external operation
1) Press the external operation key of the parameter unit.
• Rotation direction is determined by the external operation input signal.
• Set speed is determined by the external speed setting signal.
PU operation to computer link
operation
1) Mode change command to computer link mode is transmitted from the computer.
• Rotation direction and set speed are the same as those of PU operation.
Computer link operation to external
operation
1) Command to change to external mode is transmitted from the computer.
• Rotation direction is determined by the external operation input signal.
• Set speed is determined by the external speed setting signal.
Computer link operation to PU
operation
1) Select the PU operation mode with the control panel or parameter unit.
• Rotation direction and set speed are the same as those of computer link operation.
MODE
PU
EXT
FWD REV
FWD REV
STOP
RESET