AT&T 555-230-894 Marine Radio User Manual


 
Connect Power
Issue 1 September 1995
4-13
1. Connect a 10 AWG wire to the power cabinet ground discharge bar. See
Figure 4-9).
2. Repeat for each port network cabinet.
NOTE:
A Coupled Bonding Conductor (CBC) must be tie-wrapped to all
trunk cables and terminated at the coupled bonding conductor
terminal bar.
Figure 4-9. Coupled Bonding Conductor
3
3
3
8
13
4
9
14
14
5
10
15
1
6
11
2
7
12 12
1. 25-Pair tip and ring cables to network
cabinets.
2. Coupled bonding conductor terminal
block
3. Tie wraps
4. Cable shield or six spare pairs
5. Ground on carbon block protector or
equivalent
6. To external trunk interface
7. 10 AWG wire
8. Trunk cable
9. To network cabinets
10. Battery plant ground discharge bar for
DC or AC system single point ground
11. Cross-connect ground block
12. Cross-connect field
13. To other cross-connect ground blocks
14. Approved Ground
15. Couple Bonding Conductor
Figure Notes: