Mitsubishi Electronics FR-F700-NA Marine Battery User Manual


 
144
Monitor display and monitor output signal
REMARKS
By setting "0" in Pr. 52, the monitoring of output speed to fault display can be selected in sequence by .
When the operation panel (FR-DU07) is used, the displayed units are Hz, V and A only and the others are not displayed.
The monitor set in Pr. 52 is displayed in the third monitor position. (The output voltage monitor is changed.)
* The monitor displayed at powering ON is the first monitor. Display the monitor you want to display on the first monitor and hold
down for 1s. (To return to the output frequency monitor, hold down for 1s after displaying the output frequency
monitor.)
Example)When Pr. 52 is set to "20" (cumulative energization time), the monitor is displayed on the operation panel as described
below.
(2) Display set frequency during stop (Pr. 52)
When Pr. 52 is set to "100", the set frequency
monitor is displayed during a stop and the output
frequency monitor is displayed during operation.
(LED of Hz flickers during stop and is lit during
running.)
When Pr.52="100", the set frequency displayed at a
stop indicates frequency to be output when the start
command is ON.
Different from the frequency setting based on
displayed when Pr. 52="5", the value maximum/
minimum frequency and frequency jump is
displayed.
Pr. 52
0 100
During
running/stop
During
stop
During
running
Output
frequency
Output
frequency
Set
frequency
Output
frequency
Output current Output current
Output voltage Output voltage
Fault display Fault display
REMARKS
During an error, the output frequency at error occurrence appears.
During MRS, the values displayed are the same as during a stop.
Initial value
Power-ON monitor (first monitor) Second monitor Third monitor Fault monitor
With fault
Output current monitor
Output voltage monitor
Output frequency monitor
Power-ON monitor (first monitor) Second monitor Third monitor Fault monitor
With fault
Output current monitor
Output frequency monitor
Cumulative energization time monitor