Mitsubishi Electronics FR-F700-NA Marine Battery User Manual


 
180
Frequency setting by analog input (terminal 1, 2, 4)
(b) Method to adjust any point without application of a voltage (current) to across terminals 2 and 5 (4 and 5).
(To change from 4V (80%) to 5V (100%))
REMARKS
By pressing after step 6, you can confirm the current frequency setting bias/gain setting.
It cannot be confirmed after execution of step 7.
Press twice to show the next parameter ( ).
Turn to read another parameter.
Press to return to the indication (step 4).
Flicker...Parameter setting complete!!
(Adjustment completed)
C0 to C7 setting
is enabled.
Analog voltage (current)
value (%) across terminals 2 and 5
(across terminals 4 and 5)
3.
Turn until appears.
4. Press to display .
5.
Turn until ( )
appears. Set to C4 Terminal 2 frequency
setting gain.
6. Press to display the analog voltage
(current) value (%).
The parameter
number read
previously appears.
1. Confirm the RUN indication and operation
mode indication
The inverter should be at a stop.
The inverter should be in the PU operation
mode.(Using )
2. Press to choose the parameter
setting mode.
Display
Operation
The gain frequency is
reached when the analog
voltage (current) value across
terminals 2 and 5 (across terminals
4 and 5) is 100%.
7.
Turn to set the gain voltage (%).
"0V (0mA) equals to 0%, 5V (10V, 20mA) to
100%"
Remarks
The current setting at the instant of
turning is displayed.
Terminal 2 input Terminal 4 input
Terminal 2 input Terminal 4 input
8. Press to set.