Mitsubishi Electronics FR-F700-NA Marine Battery User Manual


 
64
Parameter list
Automatic
restart functions
57
Restart coasting time
0, 0.1 to 5s, 9999/
0, 0.1 to 30s, 9999
*2
0.1s 9999 152
58
Restart cushion time 0 to 60s 0.1s 1s 152
59
Remote function selection 0, 1, 2, 3, 11, 12, 13 1 0 98
60
Energy saving control selection 0, 4, 9 1 0 163
65
Retry selection 0 to 5 1 0 159
66
Stall prevention operation reduction
starting frequency
0 to 400Hz 0.01Hz 60Hz 81
Retry
67
Number of retries at fault occurrence 0 to 10, 101 to 110 1 0 159
68
Retry waiting time 0 to 10s 0.1s 1s 159
69
Retry count display erase 010159
70
Special regenerative brake duty 0 to 10% 0.1% 0% 114
71
Applied motor 0, 1, 2, 20 1 0 111
72
PWM frequency selection 0 to 15/0 to 6, 25 *2 12169
73
Analog input selection 0 to 7, 10 to 17 1 1 171
74
Input filter time constant 0 to 8 1 1 176
75
Reset selection/disconnected PU
detection/PU stop selection
0 to 3, 14 to 17,
100 to 103, 114 to 117
114186
76
Fault code output selection 0, 1, 2 1 0 161
77
Parameter write selection 0, 1, 2 1 0 189
78
Reverse rotation prevention selection 0, 1, 2 1 0 190
79
Operation mode selection 0, 1, 2, 3, 4, 6, 7 1 0 195
Simple magnetic
flux vector control
80
Motor capacity
0.4 to 55kW, 9999/
0 to 3600kW, 9999
*2
0.01/0.1kW 9999 79
90
Motor constant (R1)
0 to 50
Ω
, 9999/
0 to 400m
Ω
, 9999
*2
0.001Ω/
0.01mΩ
9999 79
Adjustable 5 points V/F
100
V/F1(first frequency) 0 to 400Hz, 9999 0.01Hz 9999 92
101
V/F1(first frequency voltage) 0 to 1000V 0.1V 0V 92
102
V/F2(second frequency) 0 to 400Hz, 9999 0.01Hz 9999 92
103
V/F2(second frequency voltage) 0 to 1000V 0.1V 0V 92
104
V/F3(third frequency) 0 to 400Hz, 9999 0.01Hz 9999 92
105
V/F3(third frequency voltage) 0 to 1000V 0.1V 0V 92
106
V/F4(fourth frequency) 0 to 400Hz, 9999 0.01Hz 9999 92
107
V/F4(fourth frequency voltage) 0 to 1000V 0.1V 0V 92
108
V/F5(fifth frequency) 0 to 400Hz, 9999 0.01Hz 9999 92
109
V/F5(fifth frequency voltage) 0 to 1000V 0.1V 0V 92
PU connector communication
117
PU communication station number 0 to 31 1 0 214
118
PU communication speed 48, 96, 192, 384 1 192 214
119
PU communication stop bit length 0, 1, 10, 11 1 1 214
120
PU communication parity check 0, 1, 2 1 2 214
121
Number of PU communication retries 0 to 10, 9999 1 1 214
122
PU communication check time
interval
0, 0.1 to 999.8s, 9999 0.1s 9999 214
123
PU communication waiting time
setting
0 to 150ms, 9999 1 9999 214
124
PU communication CR/LF selection 0, 1, 2 1 1 214
Function Parameters
Name Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer