Mitsubishi Electronics FR-F700-NA Marine Battery User Manual


 
371
Rating
7
SPECIFICATIONS
400V class
SLD is initially set.
Type FR-F740--NA
00023 00038 00052 00083 00126 00170 00250 00310 00380 00470 00620 00770 00930 01160
Applied motor capacity
(kW(HP))
*1
LD
0.75
(1)
1.5
(2)
2.2
(3)
3.7
(5)
5.5
(7.5)
7.5
(10)
11
(15)
15
(20)
18.5
(25)
22
(30)
30
(40)
37
(50)
45
(60)
55
(75)
SLD
Output
Rated capacity
(kVA)
*2
LD
1.6 2.7 3.7 5.8 8.8 12.2 17.5 22.1 26.7 32.8 43.4 53.3 64.8 80.8
SLD
Rated current (A)*3
LD
2.1
(1.8)
3.5
(3.0)
4.8
(4.1)
7.6
(6.5)
11.5
(9.8)
16
(13.6)
23
(20)
29
(25)
35
(30)
43
(37)
57
(48)
70
(60)
85
(72)
106
(90)
SLD
2.3
(2.0)
3.8
(3.2)
5.2
(4.4)
8.3
(7.1)
12.6
(10.7)
17
(14.5)
25
(21)
31
(26)
38
(32)
47
(40)
62
(53)
77
(65)
93
(79)
116
(99)
Overload current
rating
*4
LD
120% 60s, 150% 3s, 50°C (122°F) (inverse-time characteristics)
SLD
110% 60s, 120% 3s, 40°C (104°F) (inverse-time characteristics)
Rated voltage*5 Three-phase 380 to 480V
Power supply
Rated input AC voltage/frequency
Three-phase 380 to 480V 50Hz/60Hz
Permissible AC voltage fluctuation
323 to 528V 50Hz/60Hz
Permissible frequency
fluctuation
±5%
Power supply
system capacity
(kVA)
*6
Without DC reactor
2.1 4.0 4.8 8.0 11.5 16 20 27 32 41 52 65 79 99
With DC reactor
1.2 2.6 3.3 5.0 8.1 10 16 19 24 31 41 50 61 74
Protective structure
(JEM 1030)*8
Enclosed type (IP20 UL Type 1 Plenum Rated)*7 Open type (IP00)
Cooling system
Self-cooling Forced air cooling
Approx. mass (kg (lbs))
3.6
(7.9)
3.6
(7.9)
3.6
(7.9)
3.6
(7.9)
3.6
(7.9)
6.6
(14.5)
6.6
(14.5)
7.6
(16.7)
7.6
(16.7)
13
(28.7)
13
(28.7)
23
(50.7)
35
(77.2)
35
(77.2)
Type FR-F740--NA
01800 02160 02600 03250 03610 04320 04810 05470 06100 06830 07700 08660 09620 10940 12120
Applied motor capacity
(kW(HP))
*1
LD
75
(100)
90
(150)
110
(150)
132
(200)
160
(250)
185
(300)
220
(350)
250
(400)
280
(450)
315
(500)
355
(550)
400
(600)
450
(700)
500
(750)
560
(800)
SLD
90
(150)
110
(150)
132
(200)
160
(250)
185
(300)
220
(350)
250
(400)
280
(450)
315
(500)
355
(550)
400
(600)
450
(700)
500
(750)
560
(800)
630
(850)
Output
Rated capacity (kVA)*2
LD
110 137 165 198 247 275 329 366 416 464 520 586 659 733 833
SLD
137 165 198 247 275 329 366 416 464 520 586 659 733 833 923
Rated current (A)*3
LD
144
(122)
180
(153)
216
(184)
260
(221)
325
(276)
361
(306)
432
(367)
481
(408)
547
(464)
610
(518)
683
(580)
770
(654)
866
(736)
962
(817)
1094
(929)
SLD
180
(153)
216
(184)
260
(221)
325
(276)
361
(306)
432
(367)
481
(408)
547
(464)
610
(518)
683
(580)
770
(654)
866
(736)
962
(817)
1094
(929)
1212
(1030)
Overload current rating*4
LD 120% 60s, 150% 3s, 50°C (122°F) (inverse-time characteristics)
SLD
110% 60s, 120% 3s, 40°C (104°F) (inverse-time characteristics)
Voltage*5
Three-phase 380 to 480V
Power supply
Rated input AC voltage/frequency
Three-phase 380 to 480V 50Hz/60Hz
Permissible AC voltage fluctuation
323 to 528V 50Hz/60Hz
Permissible frequency fluctuation
±5%
Power supply
system
capacity
(kVA)
*6
Without DC reactor
---------------
With DC
reactor
LD
110 137 165 198 247 275 329 366 416 464 520 586 659 733 833
SLD
137 165 198 247 275 329 366 416 464 520 586 659 733 833 923
Protective structure
(JEM 1030(NEMA250-1997))*8
Open type (IP00)
Cooling system
Forced air cooling
Approx. mass (kg (lbs))
37
(81.6)
50
(110.2)
57
(125.4)
72
(158.4)
72
(158.4)
110
(242)
110
(242)
175
(385)
175
(385)
175
(385)
260
(572)
260
(572)
370
(814)
370
(814)
370
(814)
*1 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
*2 The rated output capacity indicated assumes that the output voltage is 440V.
*3 When operating the inverter with the carrier frequency set to 3kHz or more, the carrier frequency automatically decreases if the inverter
output current exceeds the value in parenthesis of the rated current. This may cause the motor noise to increase.
*4 The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated
duty, allow time for the inverter and motor to return to or below the temperatures under 100% load.
*5 The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting
range. However, the pulse voltage value of the inverter output side voltage remains unchanged at about that of the power supply.
*6 The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).
*7 When the hook of the inverter front cover is cut off for installation of the plug-in option, protective structure of the inverter changes to an open
type (the structure is no longer NEMA1).
*8 FR-DU07: IP40 (except for the PU connector)
2