Parameter List
Parameter list
4
PARAMETERS
BACnet MS/TP protocol
726
Auto Baudrate/Max Master 0 to 255 1 255 247
727
Max Info Frames 1 to 255 1 1 247
728
Device instance number (Upper 3
digit)
0 to 419 (0 to 418) 1 0 247
729
Device instance number (Lower 4
digit)
0 to 9999 (0 to 4302) 1 0 247
PID control
753
Second PID action selection
10, 11, 20, 21, 50, 51,
60, 61, 70, 71, 80, 81,
90, 91, 100, 101, 110,
111, 120, 121, 9999
19999281
754
Second PID control automatic
switchover frequency
0 to 400Hz, 9999 0.01Hz 9999 281
755
Second PID action set point 0 to 100%, 9999 0.01% 9999 281
756
Second PID proportional band 0.1 to 1000%, 9999 0.1% 100% 281
757
Second PID integral time 0.1 to 3600s, 9999 0.1s 1s 281
758
Second PID differential time 0.01 to 10.00s, 9999 0.01s 9999 281
759
PID unit selection 0 to 43, 9999 1 9999 320
760
Pre-charge fault selection 0, 1 1 0 275
761
Pre-charge ending level 0 to 100%, 9999 0.1% 9999 275
762
Pre-charge ending time 0 to 3600s, 9999 0.1s 9999 275
763
Pre-charge upper detection level 0 to 100%, 9999 0.1% 9999 275
764
Pre-charge time limit 0 to 3600s, 9999 0.1s 9999 275
765
Second pre-charge fault selection 0, 1 1 0
275,
281
766
Second pre-charge ending level 0 to 100%, 9999 0.1% 9999
275,
281
767
Second pre-charge ending time 0 to 3600s, 9999 0.1s 9999
275,
281
768
Second pre-charge upper detection
level
0 to 100%, 9999 0.1% 9999
275,
281
769
Second pre-charge time limit 0 to 3600s, 9999 0.1s 9999
275,
281
PU
774
PU/DU monitor selection 1
1 to 3, 5, 6, 8 to 14, 17,
20, 23 to 25, 40 to 42,
50 to 57, 67, 81 to 86,
100, 9999
19999
322
775
PU/DU monitor selection 2 322
776
PU/DU monitor selection 3 322
Function Parameters
Name Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting