Mitsubishi Electronics FR-F700-NA Marine Battery User Manual


 
196
Selection of operation mode and
operation location
(1) Operation mode basics
(2) Operation mode switching method
The operation mode specifies the source of the start
command and the frequency command for the
inverter.
Basically, there are following operation modes.
External operation mode: For inputting start
command and frequency command by an external
potentiometer and switches which are connected
to the control circuit terminal.
PU operation mode: For inputting start command
and frequency command by operation panel (FR-
DU07), parameter unit (FR-PU04/FR-PU07) and
RS-485 communication with PU connector.
Network operation mode (NET operation
mode): For inputting start command and
frequency command by RS-485 terminal and
communication options.
The operation mode can be selected from the
operation panel or with the communication
instruction code.
REMARKS
Either "3" or "4" may be set to select the PU/external combined operation, and these settings differ in starting method.
In the initial setting, the stop function by of the PU (FR-DU07/FR-PU07) (PU stop selection) is valid also in other than the
PU operation mode. (Pr. 75 Reset selection/disconnected PU detection/PU stop selection. Refer to page 186.)
REMARKS
For switching of operation by external terminals, refer to the following:
PU operation external interlock signal (X12 signal) . page 200
PU-external operation switch-over signal (X16) page 201
PU-NET operation switchover signal (X65), External-NET operation switchover signal (X66) page 202
Pr. 340 Communication startup mode selection page 203
1
2
3
4
5
6
7
8
9
10
Network operation mode
Network operation
mode
External
operation
mode
PU operation
mode
Personal
computer
Personal
computer
Operation
panel
Programmable
controller
Potentiometer Switch
RS-485
terminals
Inverter
Communication
option
External terminal
Switching from the network
Switch to the Network operation
mode from the Network.
Switch to the External
operation mode from
the network.
External operation
Switching from the PU
Press of
the PU to light
Network operation PU operation
Network operation PU operation
When "0, 1, or 2" is set in Pr. 340
When "10 or 12" is set in Pr. 340
Press of the PU to light
Press of
the PU to light
Press of the PU to light