Mitsubishi Electronics FR-F700-NA Marine Battery User Manual


 
206
Selection of operation mode and
operation location
(4) Operation at error occurrence
*1 Can be selected using Pr. 75 Reset selection/disconnected PU detection/PU stop selection
*2 Can be selected using Pr. 122 PU communication check time interval, Pr. 336 RS-485 communication check time interval, Pr. 502 Stop mode selection at
communication error or Pr. 539 Modbus-RTU communication check time interval.
*3 As controlled by the communication option.
*4 In the PU jog operation mode, operation is always stopped when the PU is disconnected. Whether fault (E.PUE) occurrence is allowed or not is as
set in Pr. 75 Reset selection/disconnected PU detection/PU stop selection.
*5 When Pr. 550 NET mode operation command source selection = 1 (RS-485 terminals valid) or Pr. 550 NET mode operation command source selection =
9999 and the communication option is not fitted
*6 When Pr. 550 NET mode operation command source selection = 0 (communication option valid) or Pr. 550 NET mode operation command source selection
= 9999 and the communication option is fitted
Error
Definition
Operation
Mode
Condition
(
Pr. 551
setting)
PU
Operation
External
Operation
External/PU
Combined
Operation
Mode 1
(Pr. 79 =3)
External/PU
Combined
Operation Mode
2
(Pr. 79 =4)
NET Operation
(when RS-485
terminals are
used)
*5
NET Operation
(when
communication
option is used)
*6
Inverter fault
Stop
PU
disconnection
of the PU
connector
2 (PU connector)
Stop/continued *1, 4
1 (RS-485 terminals)
Stop/continued *1
Communication
error of PU
connector
2 (PU connector)
Stop/
continued
*2
Continued
Stop/continued
*2
Continued
1 (RS-485 terminals)
Continued
Communication
error of RS-485
terminals
1 (RS-485 terminals)
Stop/
continued
*2
Continued
Stop/continued
*2
Continued
2 (PU connector)
Continued
Stop/continued
*2
Continued
Communication
error of
communication
option
Continued
Stop/continued
*3
Continued