Mitsubishi Electronics FR-F700-NA Marine Battery User Manual


 
242
Communication operation and setting
Real-time monitor
Refer to page 141 for details of the monitor description.
....Specifications differ according to the date assembled. Refer to page 400 to check the SERIAL number.
*1 The setting depends on capacities. (FR-F720-02330 (FR-F740-01160) or less/FR-F720-03160 (FR-F740-01800) or more)
*2 Input terminal monitor details
*3 Output terminal monitor details
*5 Option input terminal 1 monitor details (input terminal status of FR-A7AX) All OFF if option is not installed.
*6 Option input terminal 2 monitor details (input terminal status of FR-A7AX) All OFF if option is not installed.
*7 Option output terminal monitor details (output terminal status of FR-A7AY) All OFF if option is not installed.
b15 b0
⎯⎯⎯⎯CS RES
STOP
MRS JOG RH RM RL RT AU STR STF
b15 b0
⎯⎯⎯⎯⎯⎯⎯⎯⎯
ABC2 ABC1
FU OL IPF SU RUN
*4 When Pr.37 = "1 to 9998" or Pr. 144 = "2 to 10, 102 to 110," the unit is an integral value (one increment). (Refer to page 139)
b15 b0
X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X0
b15 b0
⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯DY
b15 b0
⎯⎯⎯⎯⎯⎯
RA3
RA2 RA1 Y6 Y5 Y4 Y3 Y2 Y1 Y0
Register Description Increments
40201 Output frequency/Speed
*4
0.01Hz/1
40202 Output current
0.01A/0.1A
*1
40203 Output voltage 0.1V
40205
Frequency setting value/Speed
setting
*4
0.01Hz/1
40206 Running speed 1r/min
40208 Converter output voltage 0.1V
40209 Regenerative brake duty 0.1%
40210
Electronic thermal relay function
load factor
0.1%
40211 Output current peak value 0.01A
/0.1A
*1
40212 Converter output voltage peak value 0.1V
40213 Input power 0.01kW/0.1kW
*1
40214 Output power 0.01kW/0.1kW *1
40215 Input terminal status *2
40216 Output terminal status
*3
40217 Load meter
0.1%
40220 Cumulative energization time
1h
40223 Actual operation time
1h
40224 Motor load factor
0.1%
40225 Cumulative power 1kWh
40250 Power saving effect Variable
40251 Cumulative saving power Variable
40252 PID set point
0.1%
40253 PID measured value
0.1%
40254 PID deviation
0.1%
40258
Option input terminal status 1
*5
40259
Option input terminal status 2
*6
40260
Option output terminal status
*7
40267 PID measured value 2 0.1%
40277
32-bit cumulative power
(lower 16-bit)
1kWh
40278
32-bit cumulative power
(upper 16-bit)
1kWh
40279
32-bit cumulative power
(lower 16-bit)
0.01kWh/
0.1kWh *1
40280
32-bit cumulative power
(upper 16-bit)
0.01kWh/
0.1kWh
*1
Register Description Increments