Mitsubishi Electronics FR-F700-NA Marine Battery User Manual


 
11
Installation of the inverter and
enclosure design
1
OUTLINE
(2) Clearances around the inverter
To ensure ease of heat dissipation and maintenance, leave at least the shown clearances around the inverter. At least the
following clearances are required under the inverter as a wiring space, and above the inverter as a heat dissipation space.
(3) Inverter mounting orientation
Mount the inverter on a wall as specified. Do not mount it horizontally or any other way.
(4) Above the inverter
Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed above the inverter
should be heat resistant.
(5) Arrangement of multiple inverters
(6) Placement of ventilation fan and inverter
REMARKS
For replacing the cooling fan of the FR-F740-04320 or more, 30cm(11.8 inches) of space is necessary in front of
the inverter. Refer to page 360 for fan replacement.
When multiple inverters are placed in the same
enclosure, generally arrange them horizontally as
shown in the right figure (a). When it is inevitable to
arrange them vertically to minimize space, take such
measures as to provide guides since heat from the
bottom inverters can increase the temperatures in
the top inverters, causing inverter failures.
When mounting multiple inverters, fully take caution
not to make the surrounding air temperature of the
inverter higher than the permissible value by
providing ventilation and increasing the enclosure
size.
Arrangement of multiple inverters
Heat generated in the inverter is blown up from the bottom of
the unit as warm air by the cooling fan. When installing a
ventilation fan for that heat, determine the place of ventilation
fan installation after fully considering an air flow. (Air passes
through areas of low resistance. Make an airway and airflow
plates to expose the inverter to cool air.)
Placement of ventilation fan and inverter
Clearances
Surrounding air temperature and humidity
Measurement
position
Measurement
position
Inverter
Leave enough clearances as a
cooling measure.
Humidity: 90% RH maximum
FR-F720-02330 or less
FR-F740-01160 or less
FR-F720-03160 or more
FR-F740-01800 or more
5cm
(1.97inches)
5cm
(1.97inches)
5cm
(1.97inches)
10cm
(3.94inches)
or more
20cm (7.87inches)
or more
20cm (7.87inches)
or more
10cm
(3.94inches)
or more
5cm
(1.97inches)
or more *
5cm
(1.97inches)
or more *
10cm
(3.94inches)
or more
10cm
(3.94inches)
or more
Temperature: -10°C to 50°C (14°F to 122°F)
(LD)
-10°C to 40°C (14°F to 104°F)
(SLD)
(front)
* 1cm (0.39 inches) or more for FR-F720-00167, FR-740-
00083 or less
Clearances (side)
*
Inverter
5cm
(1.97inches)
or more
* 1cm (0.39 inches) or more for FR-
F720-00167, FR-740-00083 or less
Guide Guide
Enclosure Enclosure
Guide
(a) Horizontal arrangement
(b) Vertical arrangement
Inverter
Inverter
Inverter
Inverter
Inverter
Inverter
Inverter Inverter
<Good example> <Bad example>