Mitsubishi Electronics FR-F700-NA Marine Battery User Manual


 
316
Setting from the parameter unit, operation panel
(1) Using the setting dial like a potentiometer to set the frequency.
Operation example Changing the frequency from 0Hz to 60Hz during operation
REMARKS
If the display changes from flickering "60.00" to "0.00", the setting of Pr. 161 Frequency setting/key lock operation selection may not
be "1".
Independently of whether the inverter is running or at a stop, the frequency can be set by merely turning the dial.
When the frequency is changed, it will be stored in EEPROM as the set frequency after 10s.
CAUTION
When using setting dial, the frequency goes up to the set value of Pr.1 Maximum frequency (initial value :120Hz (FR-F720-02330
(FR-F740-01160) or less) /60Hz (FR-F720-03160 (FR-F740-01800) or more ).
DisplayOperation
PU indication is lit.
Flicker ··· Parameter setting complete!!
7. Press to set.
The parameter number
previously read appears.
1. Screen at powering ON
The monitor display appears.
2. Press to choose the PU operation
mode.
3. Press to choose the parameter
setting mode.
The frequency flickers for about 5s.
8. Mode/monitor check
Press twice to choose
monitor/frequency monitor.
9. Press (or ) to start the inverter.
10. Turn until " " appears.
The flickering frequency is the set frequency.
You need not press .
4. Turn until (Pr. 161) appears.
5. Press to read the present set value.
" " (initial value) appears.
6. Turn to change it
to the setting value " ".