Mitsubishi Electronics FR-F700-NA Marine Battery User Manual


 
250
Communication operation and setting
(5) Supported property of BACnet standard object type
R: Read only W: Read/Write (Commandable values not supported) C: Read/Write (Commandable values supported)
*1 This property is commandable for some instances of this object. Otherwise it is read/write.
*2 This property is supported only for instances of this object where the Present Value property is commandable.
Object
Property
Analog Input
Analog Output
Analog Value
Binary Input
Binary Output
Binary Value
Device
APDU Timeout R
Application Software Version R
Database Revision R
Device Address Binding R
Event State RRRRRR
Firmware Revision R
Max APDU Length Accepted R
Max Info Frames W
Max Master W
Model Name R
Number of APDU Retries R
Object Identifier RRRRRRR
Object List R
Object Name RRRRRRR
Object Type RRRRRRR
Out Of Service RRRRRR
Polarity R R
Present Value R C C
*1 RCC *1
Priority Array R R *2 RR *2
Protocol Object Types Supported R
Protocol Revision R
Protocol Services Supported R
Protocol Version R
Relinquish Default R R
*2 RR *2
Segmentation Supported R
Status Flags RRRRRR
System Status R
Unit R R R
Vendor Identifier R
Vendor Name R