Parameter list
Communication
549
Protocol selection 0, 1, 2 1 1 232
550
NET mode operation command
source selection
0, 1, 9999 1 9999 204
551
PU mode operation command source
selection
1, 2 1 2 204
PID
control
553
PID deviation limit 0 to 100.0%, 9999 0.1% 9999 261
554
PID signal operation selection 0 to 3, 10 to 13 1 0
261,
283
Current average
monitor
555
Current average time 0.1 to 1.0s 0.1s 1s 305
556
Data output mask time 0.0 to 20.0s 0.1s 0s 305
557
Current average value monitor signal
output reference current
0 to 500A/0 to 3600A
*2
0.01/0.1A
*2
Rated
inverter
current
305
563
Energization time carrying-over times (0 to 65535) 1 0 141
564
Operating time carrying-over times (0 to 65535) 1 0 141
Multiple
rating
570
Multiple rating setting 0, 1 1 0 86
571
Holding time at a start 0.0 to 10.0s, 9999 0.1s 9999 104
573
4mA input check selection 1, 2, 3, 4, 9999 1 9999 182
PID control
575
Output interruption detection time 0 to 3600s, 9999 0.1s 1s
261,
283
576
Output interruption detection level 0 to 400Hz 0.01Hz 0Hz
261,
283
577
Output interruption cancel level 900 to 1100% 0.1% 1000%
261,
283
Pump function
578
Auxiliary motor operation selection 0 to 3 1 0 283
579
Motor connection function selection 0 to 3 1 0 283
580
MC switching interlock time 0 to 100s 0.1s 1s 283
581
Start waiting time 0 to 100s 0.1s 1s 283
582
Auxiliary motor connection-time
deceleration time
0 to 3600/360s, 9999 0.1/0.01s 1s 283
583
Auxiliary motor disconnection-time
acceleration time
0 to 3600/360s, 9999 0.1/0.01s 1s 283
584
Auxiliary motor 1 starting frequency 0 to 400Hz 0.01Hz 60Hz 283
585
Auxiliary motor 2 starting frequency 0 to 400Hz 0.01Hz 60Hz 283
586
Auxiliary motor 3 starting frequency 0 to 400Hz 0.01Hz 60Hz 283
587
Auxiliary motor 1 stopping frequency 0 to 400Hz 0.01Hz 0Hz 283
588
Auxiliary motor 2 stopping frequency 0 to 400Hz 0.01Hz 0Hz 283
589
Auxiliary motor 3 stopping frequency 0 to 400Hz 0.01Hz 0Hz 283
590
Auxiliary motor start detection time 0 to 3600s 0.1s 5s 283
591
Auxiliary motor stop detection time 0 to 3600s 0.1s 5s 283
611
Acceleration time at a restart 0 to 3600s, 9999 0.1s 5/15s *2 152
Speed
smoothing
control
653
Speed smoothing control 0 to 200% 0.1% 0 170
654
Speed smoothing cutoff frequency 0 to 120Hz 0.01Hz 20Hz 170
665
Regeneration avoidance frequency
gain
0 to 200% 0.1% 100% 298
Function Parameters
Name Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer