Mitsubishi Electronics FR-F700-NA Marine Battery User Manual


 
322
Setting of FR-PU07-01
4.24.4 3-line monitor selection (Pr. 774 to Pr.776)
*1 The monitor is displayed as Pr. 774 = "1," Pr. 775 = "2," and Pr. 776 = "3" when a parameter unit other than FR-DU07 is used.
*2 The monitor is displayed as Pr. 774 = "1," Pr. 775 = "2," and Pr. 776 = "3" when the monitor selection is valid.
*3 The setting is available when using PLC function. Refer to the FR-F700 PLC function programming manual for details of the PLC function.
For the parameter unit (FR-PU07)/operation panel (FR-DU07), the first, second, and third monitors can be
changed. When using FR-PU07-01, the monitored items, which are set by Pr.774 to Pr.776, can be displayed in
the 3-line monitor.
The Pr.52 DU/PU main display data selection setting is invalid when Pr.774 to Pr.776
9999. Monitored item names
are displayed during monitoring (Monitor name display in the 3-line monitor is available only for FR-PU07-01).
Parameter
Number
Name
Initial
Value
Setting
Range
Description
774
PU/DU monitor
selection 1
9999
1 to 3, 5, 6, 8 to
14, 17, 20,
23 to 25, 40 to
42, 50 to 57,
67, 81 to 86,
100, 9999
Select the monitored item to be displayed on the first monitor
(first row in the 3-line monitor).
775
PU/DU monitor
selection 2
Select the monitored item to be displayed on the second
monitor (second row in the 3-line monitor).
776
PU/DU monitor
selection 3
Select the monitored item to be displayed on the third monitor
(third row in the 3-line monitor).
Parameters referred to
Pr. 52 DU/PU main display data selection Refer to page 141
Pr. 59 Remote function selection Refer to page 98
Pr. 73 Analog input selection Refer to page 171
Pr. 79 Operation mode selection Refer to page 195
Pr. 133 PID action set point Refer to page 261
Pr. 160 User group read selection Refer to page 190
Pr. 178 to Pr. 189 (input terminal function selection) Refer to page 122
Pr. 190 to Pr. 196 (output terminal function selection) Refer to page 128
C2 (Pr. 902) to C7 (Pr. 905) Frequency setting voltage (current) bias/gain Refer to page 177
C42 (Pr. 934) to C45 (Pr. 935) (PID control) Refer to page 261
Setting Monitor item
1 Output frequency
2 Output current
3 Output voltage
5 Frequency setting value
6 Running speed
8 Converter output voltage
9 Regenerative brake duty
10
Electronic thermal relay
function load factor
11 Output current peak value
12
Converter output voltage peak
value
13 Input power
14 Output power
17 Load meter
20 Cumulative energization time
23 Actual operation time
24 Motor load factor
25 Cumulative power
40
PLC function user monitor 1
*3
41
PLC function user monitor 2
*3
42
PLC function user monitor 3
*3
50 Power saving effect
51 Cumulative saving power
52 PID set point
53 PID measured value
54 PID deviation
55
*1
I/O terminal status
56
*1
Option input terminal status
57
*1
Option output terminal status
67 PID measured value 2
81 BACnet reception status
82 BACnet token pass counter
83 BACnet valid APDU counter
Setting Monitor item
84
BACnet communication error
counter
85 Terminal CA output level
86 Terminal AM output level
100
Set frequency before
operation
9999
*2
No selection
Setting Monitor item
How the monitor is displayed when
Pr. 759 = "4," Pr. 774 = "52," Pr. 775 = "53,"
and Pr. 776 = "54"
2+&UGV25+
2+&XCN25+
2+&FGX25+
56((9&*#0&