Mitsubishi Electronics FR-A720-0.4k to 90k Marine Battery User Manual


 
149
Adjustment of the output torque
(current) of the motor
4
PARAMETERS
(1) Selection method of Advanced magnetic flux vector control
REMARKS
· When higher accuracy operation is necessary, set online auto tuning after performing offline auto tuning and select Real
sensorless vector control.
Perform secure wiring.
(Refer to page 14)
Set the motor capacity and the number of motor poles.
(Pr. 80, Pr. 81) (Refer to page 92)
Test run
Set the motor. (Pr. 71)
Set the operation command. (Refer to page 313)
As required
· Perform offline auto tuning. (Pr. 96) (refer to page 189)
· Select online auto tuning. (Pr. 95) (refer to page 199)
Select the start command and speed command.
(1) Start command
1. Operation panel :
Setting by pressing / of the operation panel
2. External command : Setting by forward rotation or reverse
rotation command (terminal STF or STR)
(2) Speed command
1. Operation panel :
Setting by of the operation panel
2. External analog command (terminal 2 or 4) :
Give a speed command using the analog signal input to
terminal 2 (or terminal 4).
3. Multi-speed command :
The external signals (RH, RM, RL) may also be used to give
speed command.
Set motor capacity (kW) in Pr. 80 Motor capacity and the number
of motor poles (number of poles) in Pr. 81 Number of motor poles.
(V/F control is performed when the setting is "9999" (initial value).)
Motor Pr. 71 Setting *1 REMARKS
Mitsubishi standard
motor
Mitsubishi high
efficiency motor
SF-JR 0 (initial value)
SF-JR 4P 1.5kW or lower
20
SF-HR 40
Others 3 Offline auto tuning is necessary.
*2
Mitsubishi constant-
torque motor
SF-JRCA 4P 1
SF-HRCA 50
Others (SF-JRC, etc.) 13 Offline auto tuning is necessary.
*2
Other
manufacturer's
standard motor
3 Offline auto tuning is necessary.
*2
Other
manufacturer's
constant torque
motor
13 Offline auto tuning is necessary.
*2
*1 For other settings of Pr. 71 , refer to page 187.
*2 Refer to page 189 for offline auto tuning.