Mitsubishi Electronics FR-A720-0.4k to 90k Marine Battery User Manual


 
183
Selection and protection of a motor
4
PARAMETERS
4.13 Selection and protection of a motor
4.13.1 Motor protection from overheat (Electronic thermal relay function) (Pr. 9, Pr. 51)
*1 The initial value of the 0.4K and 0.75K is set to 85% of the rated inverter current.
*2 When parameter is read using the FR-PU04, a parameter name different from an actual parameter is displayed.
(1) Electronic thermal relay function operation characteristic (THM)
Purpose Parameter that must be Set Refer to Page
Motor protection from overheat Electronic thermal O/L relay Pr. 9, Pr. 51 183
Use the constant torque motor Applied motor Pr. 71 187
The motor performance can be
maximized for operation in magnetic
flux vector control system
Offline auto tuning
Pr. 82 to Pr. 84,
Pr. 90 to Pr. 94, Pr. 96
189
High accuracy operation unaffected
by the motor temperature and stable
operation with high torque down to
ultra low speed are performed
Online auto tuning Pr. 95, Pr. 574 199
Set the current of the electronic thermal O/L relay to protect the motor from overheat. This feature provides the
optimum protective characteristics, including reduced motor cooling capability, at low speed.
Parameter
Number
Name Initial Value Setting Range Description
9
Electronic thermal
O/L relay
Rated inverter
current
*1
55K or lower 0 to 500A
Set the rated motor current.
75K or higher 0 to 3600A
51
Second electronic
thermal O/L relay
*2
9999
55K or lower 0 to 500A
Valid when the RT signal is ON.
Set the rated motor current.
75K or higher 0 to 3600A
9999
Second electronic thermal O/L relay invalid
[Electronic thermal relay function operation characteristic (E.THM)]
This function detects the overload (overheat) of the
motor, stops the operation of the inverter's output
transistor, and trips. (The operation characteristic is
shown on the left)
Set the rated current [A] of the motor in Pr. 9. (If the
motor has both 50Hz and 60Hz rating and the Pr. 3
Base frequency is set to 60Hz, set the 1.1 times of the
60Hz rated motor current.)
Set "0" in Pr. 9 when you do not want to activate the
electronic thermal relay function, e.g. when using an
external thermal relay with the motor. (Note that the
output transistor protection of the inverter functions
(E.THT).)
When using the Mitsubishi constant-torque motor
1) Set "1" or any of "13" to "18", "50", "53", "54" in
Pr. 71
.
(This provides a 100% continuous torque characteristic
in the low-speed range.)
2) Set the rated current of the motor in Pr. 9.
*1 When 50% of the rated inverter current (current value) is set in Pr. 9
*2 The % value denotes the percentage to the rated inverter current. It
is not the percentage to the motor rated current.
*3 When you set the electronic thermal relay function dedicated to the
Mitsubishi constant-torque motor, this characteristic curve applies
to operation at 6Hz or higher. (Refer to page 187 for the operation
characteristic.)
CAUTION
Fault by electronic thermal relay function is reset by inverter power reset and reset signal input. Avoid unnecessary reset and
power-off.
When using multiple motors with one inverter, or using a multi-pole motor or a specialized motor, provide an external thermal
relay (OCR) between the inverter and motor. And for the setting of the thermal relay, add the line-to line leakage current (refer to
page 52) to the current value on the motor rating plate. For low-speed operation where the cooling capability of the motor
reduces, it is recommended to use a thermal protector or thermistor-incorporated motor.
When the difference between the inverter and motor capacities is large and the setting is small, the protective characteristics of
the electronic thermal relay function will be deteriorated. In this case, use an external thermal relay.
Since a thermal protector is built in a motor dedicated for vector control (SF-V5RU), set "0" in Pr. 9 to use the motor
Electronic thermal relay may not function when 5% or less of inverter rated current is set to electronic thermal relay setting.
Electronic thermal relay
function for transistor
protection
52.5%
105%
50
100
150
60
120
180
240
50
60
70
6Hz
20Hz
10Hz
6Hz
0.5Hz
30Hz or more*
3
20Hz
10Hz
0.5Hz
Pr. 9 = 50% setting of
inverter rating*
1.2
Pr. 9 = 100% setting
of inverter rating*
2
(s) unit display in this region
(min) unit display in
this region
Operation time (min)Operation time (s)
Characteristic when
electronic thermal relay
function for motor
protection is turned off
(When Pr. 9 setting is 0(A))
30Hz
or more*
3
Inverter output current(%)
(% to the rated inverter current)
Operation region
Region on the right of
characteristic curve
Non-operation region
Region on the left of
characteristic curve