Selection and protection of a motor
4
PARAMETERS
(4) Utilizing or changing offline auto tuning data for use
The data measured in the offline auto tuning can be read and utilized or changed.
<Operating procedure>
1)Set Pr. 71 according to the motor used.
*1 For other settings of Pr. 71, refer to page 187.
2)In the parameter setting mode, read the following parameters and set desired values.
Motor Pr. 71 Setting*
Mitsubishi standard motor
Mitsubishi high efficiency
motor
SF-JR, SF-TH 4
SF-JR 4P 1.5kW or lower 24
SF-HR 44
Others 4
Mitsubishi constant-torque
motor
SF-JRCA 4P
SF-TH (constant torque)
14
SF-HRCA 54
Others (SF-JRC, etc.) 14
Vector control dedicated
motor
SF-V5RU (1500r/min series)
SF-THY
34
SF-V5RU (except for 1500r/min series) 14
Other manufacturer's
standard motor
4
Other manufacturer's
constant torque motor
14
Parameter
Number
Name Setting Range
Setting
Increments
Initial
Value
82 Motor excitation current 0 to ***, 9999 1 9999
90 Motor constant (R1) 0 to ***, 9999 1 9999
91 Motor constant (R2) 0 to ***, 9999 1 9999
92 Motor constant (L1) 0 to ***, 9999 1 9999
93 Motor constant (L2) 0 to ***, 9999 1 9999
94 Motor constant (X) 0 to ***, 9999 1 9999
859 Torque current 0 to ***, 9999 1 9999
REMARKS
· The display units of the motor constants read using Pr. 684 Tuning data unit switchover can be changed. Note that parameter
values cannot be changed.
· When "9999" is set in Pr. 82, Pr. 90 to Pr. 94, Pr. 455, Pr. 458 to Pr. 462, Pr. 859, Pr. 860, Mitsubishi motor (SF-JR, SF-HR, SF-
JRCA, SF-HRCA, SF-V5RU (1500r/min series), etc.) constants are used.
· As the motor constants measured in the offline auto tuning have been converted into internal data (****), refer to the following
setting example when making setting:
Setting example To slightly increase Pr. 90 value (5%)
When Pr. 90 is displayed "2516",
set 2642, i.e. 2516
× 1.05 = 2641.8, in Pr. 90 .
(The value displayed has been converted into a value for internal use. Hence, simple addition of a given
value to the displayed value has no significance.)
Pr. 684
Setting
Pr. 82,
Pr. 455
Pr. 90,
Pr. 458
Pr. 91,
Pr. 459
Pr. 92,
Pr. 460
Pr. 93,
Pr. 461
Pr. 94,
Pr. 462
Pr. 859,
Pr. 860
0 Internal data converted value
1
55K or lower 0.01A 0.001Ω 0.001Ω 0.1mH 0.1mH 0.1% 0.01A
75K or higher 0.1A 0.01mΩ 0.01mΩ 0.01mH 0.01mH 0.01% 0.1A