Monitor display and monitor output signal
4
PARAMETERS
4.16 Monitor display and monitor output signal
4.16.1 Speed display and speed setting (Pr. 37, Pr. 144, Pr. 505, Pr. 811)
* The maximum value of the setting range differs according to the Pr. 1 Maximum frequency and Pr. 505 Speed setting reference settings
and it can be calculated from the following formula.
Maximum setting value of Pr. 37 <
Note that the maximum setting value of Pr. 37 is 9998 if the result of the above formula exceeds 9998.
Purpose Parameter that must be Set Refer to Page
Display motor speed
Set speed
Speed display and speed
setting
Pr. 37, Pr. 144, Pr. 505, Pr. 811 251
Change PU monitor display data
DU/PU main display data
selection
Cumulative monitor clear
Pr. 52, Pr. 170, Pr. 171, Pr. 268, Pr. 891 253
Change of the monitor output
from terminal FM and AM
Terminal FM, AM function
selection
Pr. 54, Pr. 158, Pr. 291, Pr. 866, Pr. 867 253
Set the reference of the monitor
output from terminal FM and AM
Setting of reference of
terminal FM and AM
Pr. 55, Pr. 56, Pr. 291, Pr. 866, Pr. 867 259
Adjust terminal FM, AM outputs
Terminal FM, AM
calibration
Pr. 900, Pr. 901 263
You can change the PU (FR-DU07/FR-PU04/FR-PU07) monitor display or frequency setting to motor speed or
machine speed.
Parameter
Number
Name
Initial
Value
Setting
Range
Description
37 Speed display 0
0 Frequency display, setting
1 to 9998* Set the machine speed at Pr. 505.
144 Speed setting switchover 4
0, 2, 4, 6, 8,
10, 102, 104,
106, 108, 110
Set the number of motor poles when displaying the motor speed.
505 Speed setting reference 60Hz 1 to 120Hz Set the reference speed for Pr. 37.
811 Set resolution switchover 0
Speed setting and running
speed monitor increments from
the PU, RS-485 communication
or communication option.
Torque limit setting increments
Pr. 22, Pr. 812 to Pr. 817
0 1r/min
0.1%
1 0.1r/min
10 1r/min
0.01%
11 0.1r/min
65535 × Pr. 505
Setting value of Pr. 1 (Hz)