Mitsubishi Electronics FR-A720-0.4k to 90k Marine Battery User Manual


 
404
Causes and corrective actions
5.3 Causes and corrective actions
(1) Error message
A message regarding operational troubles is displayed. Output is not shut off.
....... Specifications differ according to the date assembled. Refer to page 484 to check the SERIAL number.
Operation Panel
Indication
HOLD
Name
Operation panel lock
Description
Operation lock mode is set. Operation other than is invalid. (Refer to page 395.)
Check point
--------------
Corrective action
Press for 2s to release lock.
Operation Panel
Indication
LOCD
Name
Password locked
Description
Password function is active. Display and setting of parameter is restricted.
Check point --------------
Corrective action
Enter the password in Pr. 297 Password lock/unlock to unlock the password function before operating.
(Refer to page 310.)
Operation Panel
Indication
Er1
Name
Write disable error
Description
· You attempted to make parameter setting when Pr. 77 Parameter write selection has been set to
disable parameter write.
· Frequency jump setting range overlapped.
· Adjustable 5 points V/F settings overlapped
· The PU and inverter cannot make normal communication
Check point
· Check the setting of Pr. 77 Parameter write selection (Refer to page 307.)
· Check the settings of Pr. 31 to 36 (frequency jump). (Refer to page 158.)
· Check the settings of Pr. 100 to Pr. 109 (adjustable 5 points V/F). (Refer to page 164.)
· Check the connection of the PU and inverter.
Operation Panel
Indication
Er2
Name
Write error during operation
Description
When parameter write was performed during operation with a value other than "2" (writing is enabled
independently of operating status in any operation mode) is set in Pr. 77 and the STF (STR) is ON.
Check point
· Check the Pr. 77 setting. (Refer to page 307.)
· Check that the inverter is not operating.
Corrective action
·Set "2" in Pr. 77.
· After stopping operation, make parameter setting.
Operation Panel
Indication
Er3
Name
Calibration error
Description
Analog input bias and gain calibration values are too close.
Check point
Check the settings of C3, C4, C6 and C7 (calibration functions). (Refer to page 294.)