41
Connection of stand-alone option units
2
WIRING
* Do not remove the jumper across terminal P/+ and P1 except when connecting a DC reactor.
When the regenerative brake transistor is damaged, the following sequence is recommended to prevent overheat
and burnout of the brake resistor.
*1 Since the 11K or higher inverter is not provided with the PX terminal, a jumper is not need to be removed.
*2 Refer to the table below for the type number of each capacity of thermal relay and the diagram below for the connection. (Always install a thermal
relay when using the 11K or higher)
FR-A720-11K, FR-A740-11K, 15K FR-A720-15K to 22K, FR-A740-18.5K, 22K
Power Supply
Voltage
High-Duty Brake
Resistor
Thermal Relay Type
(Mitsubishi product)
Contact Rating
200V
FR-ABR-0.4K TH-N20CXHZ-0.7A
110V 5AAC,
220V 2AAC(AC-11 class)
110V 0.5ADC,
220V 0.25ADC(DC-11 class)
FR-ABR-0.75K TH-N20CXHZ-1.3A
FR-ABR-2.2K TH-N20CXHZ-2.1A
FR-ABR-3.7K TH-N20CXHZ-3.6A
FR-ABR-5.5K TH-N20CXHZ-5A
FR-ABR-7.5K TH-N20CXHZ-6.6A
FR-ABR-11K TH-N20CXHZ-11A
FR-ABR-15K TH-N20CXHZ-11A
FR-ABR-22K TH-N60-22A
400V
FR-ABR-H0.4K TH-N20CXHZ-0.24A
FR-ABR-H0.75K TH-N20CXHZ-0.35A
FR-ABR-H1.5K TH-N20CXHZ-0.9A
FR-ABR-H2.2K TH-N20CXHZ-1.3A
FR-ABR-H3.7K TH-N20CXHZ-2.1A
FR-ABR-H5.5K TH-N20CXHZ-2.5A
FR-ABR-H7.5K TH-N20CXHZ-3.6A
FR-ABR-H11K TH-N20CXHZ-6.6A
FR-ABR-H15K TH-N20CXHZ-6.6A
FR-ABR-H22K TH-N20-9A
CAUTION
The brake resistor connected should only be the dedicated brake resistor.
The jumper across terminals PR and PX (7.5K or lower) must be disconnected before connecting the dedicated brake resistor.
Doing so may damage the inverter.
Brake resistor cannot be used with the brake unit, high power factor converter, power supply regeneration converter, etc.
Jumper *
Terminal P/+
Terminal PR
Brake resistor
Connect the brake resistor
across terminals P/+ and PR.
Terminal P/+
Terminal PR
Brake resistor
Jumper
*
Connect the brake resistor
across terminals P/+ and PR.
R
MC
Power
Supply
High-duty
brake resistor
(FR-ABR)
Thermal
relay
(OCR)(*2)
Inverter
PX
PR
P/+
S/L2
T/L3
R/L1
Disconnect jumper. (*1)
MC
Power
Supply
T
F
ON
OFF
MC
MC
OCR
Contact
<Example 1>
<Example 2>
PX
PR
P/+
S/L2
T/L3
R/L1
Inverter
(OCR)(*2)
Thermal
relay
(FR-ABR)
High-duty
brake resisto
r
R
Disconnect jumper. (*1)
B
C
T
F
ON
OFF
OCR
Contact
MC
MC
To the inverter
P/+ terminal
To the AB
R
TH-N20
1/L
1
5/L
3
2/T
1
6/T
3