Mitsubishi Electronics FR-A720-0.4k to 90k Marine Battery User Manual


 
356
Communication operation and setting
Real-time monitor
Refer to page 253 for details of the monitor description.
...........Specifications differ according to the date assembled. Refer to page 484 to check the SERIAL number.
*1 The setting depends on capacities. (55K or lower / 75K or higher)
*2 When Pr. 37 = "1 to 9998" or Pr. 144 = "2 to 10, 102 to 110," the unit is an integral value (one increment). (Refer to page 251)
*3 Input terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0, —: undetermined value)
*4 Output terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0, —: undetermined value)
*5 Details of option input terminal monitor 1 (input terminal status of FR-A7AX when the terminal is ON: 1, when the terminal is OFF: 0)-all terminals
are OFF when an option is not fitted
*6 Details of option input terminal monitor 2 (input terminal status of FR-A7AX when the terminal is ON: 1, when the terminal is OFF: 0, —:
undetermined value)-all terminals are OFF when an option is not fitted
*7 Details of option output terminal monitor (output terminal status of FR-A7AY/A7AR when the terminal is ON: 1, when the terminal is OFF: 0, —:
undetermined value)-all terminals are OFF when an option is not fitted
b15 b0
⎯⎯⎯⎯CS RES STOP MRS JOG RH RM RL RT AU STR STF
b15 b0
⎯⎯⎯⎯⎯⎯⎯⎯⎯ABC2 ABC1 FU OL IPF SU RUN
b15 b0
X15 X14 X13 X12 X11 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 X0
b15 b0
⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯DY
b15 b0
⎯⎯⎯⎯⎯⎯RA3RA2RA1Y6Y5Y4Y3Y2Y1Y0
Register Definition
Increments
40201
Output frequency/
speed
*2
0.01Hz/1
40202 Output current
0.01A/
0.1A
*1
40203 Output voltage 0.1V
40205
Frequency setting
value/speed setting
*2
0.01Hz/1
40206 Running speed 1r/min
40207 Motor torque 0.1%
40208
Converter output
voltage
0.1V
40209
Regenerative brake
duty
0.1%
40210
Electronic thermal
relay function load
factor
0.1%
40211
Output current peak
value
0.01A/
0.1A
*1
40212
Converter output
voltage peak value
0.1V
40213 Input power
0.01kW/
0.1kW
*1
40214 Output power
0.01kW/
0.1kW
*1
40215
Input terminal
status
*3
40216
Output terminal
status
*4
40217 Load meter 0.1%
40218
Motor excitation
current
0.01A/
0.1A
*1
40219 Position pulse
40220
Cumulative
energization time
1h
40222 Orientation status
40223
Actual operation
time
1h
40224 Motor load factor 0.1%
40225 Cumulative power 1kWh
40232 Torque command 0.1%
Register Definition
Increments
40233
Torque current
command
0.1%
40234 Motor output
0.01/
0.1kW
*1
40235 Feedback pulse
40246
Motor temperature
1°C
40250 Power saving effect Variable
40251
Cumulative saving
power
Variable
40252 PID set point 0.1%
40253
PID measured
value
0.1%
40254 PID deviation value 0.1%
40258
Option input
terminal status1
*5
40259
Option input
terminal status2
*6
40260
Option output
terminal status
*7
Register Definition
Increments