72
Parameter List
Parameter List
Frequency
detection
41 Up-to-frequency sensitivity 0 to 100% 0.1% 10%
246
42 Output frequency detection 0 to 400Hz 0.01Hz 6Hz
246
43
Output frequency detection for reverse
rotation
0 to 400Hz, 9999 0.01Hz 9999
246
Second functions
44 Second acceleration/deceleration time 0 to 3600/360s 0.1/0.01s 5s 172
45 Second deceleration time 0 to 3600/360s, 9999 0.1/0.01s 9999 172
46
Second torque boost 0 to 30%, 9999
0.1% 9999 146
47
Second V/F (base frequency) 0 to 400Hz, 9999
0.01Hz 9999 159
48
Second stall prevention operation
current
0 to 220%
0.1% 150% 152
49
Second stall prevention operation
frequency
0 to 400Hz, 9999
0.01Hz 0Hz 152
50
Second output frequency detection 0 to 400Hz
0.01Hz 30Hz 246
51 Second electronic thermal O/L relay
0 to 500A, 9999/
0 to 3600A, 9999
*2
0.01/0.1A *2 9999 183
Monitor functions
52
DU/PU main display data selection
0, 5 to 14, 17 to 20,
22 to 25, 32 to 35, 39, 46,
50 to 57, 100
1 0 253
54
FM terminal function selection
1 to 3, 5 to 14, 17, 18,
21, 24, 32 to 34, 46, 50,
52, 53
1 1 253
55
Frequency monitoring reference 0 to 400Hz
0.01Hz 60Hz 259
56
Current monitoring reference 0 to 500/0 to 3600A *2
0.01/0.1A *2
Rated inverter
current
259
Automatic restart
57 Restart coasting time
0, 0.1 to 5s, 9999/
0, 0.1 to 30s, 9999
*2
0.1s 9999 266
58
Restart cushion time 0 to 60s
0.1s 1s 266
⎯ 59
Remote function selection 0, 1, 2, 3
1 0 169
⎯ 60
Energy saving control selection 0, 4
1 0 278
Automatic acceleration/
deceleration
61 Reference current
0 to 500A, 9999/
0 to 3600A, 9999
*2
0.01A/0.1A *2 9999
163,
180
62 Reference value at acceleration 0 to 220%, 9999 0.1% 9999 180
63 Reference value at deceleration 0 to 220%, 9999 0.1% 9999 180
64 Starting frequency for elevator mode 0 to 10Hz, 9999 0.01Hz 9999 163
⎯
65
Retry selection 0 to 5
1 0 273
⎯
66
Stall prevention operation reduction
starting frequency
0 to 400Hz 0.01Hz 60Hz 152
Retry
67
Number of retries at fault occurrence 0 to 10, 101 to 110
1 0 273
68
Retry waiting time 0 to 10s
0.1s 1s 273
69
Retry count display erase 0
1 0 273
⎯
70
Special regenerative brake duty 0 to 30%/0 to 10% *2
0.1% 0% 207
⎯ 71
Applied motor
0 to 8, 13 to 18, 20, 23,
24, 30, 33, 34, 40, 43, 44,
50, 53, 54
1 0
148,
187
⎯
72 PWM frequency selection 0 to 15/0 to 6, 25 *2 1 2 284
⎯
73 Analog input selection 0 to 7, 10 to 17 1 1 290
⎯
74 Input filter time constant 0 to 8 1 1 292
⎯ 75
Reset selection/disconnected PU
detection/PU stop selection
0 to 3, 14 to 17
1 14 305
⎯
76
Fault code output selection 0, 1, 2
1 0 275
⎯ 77
Parameter write selection 0, 1, 2
1 0 307
⎯ 78
Reverse rotation prevention selection 0, 1, 2
1 0 308
⎯
79
Operation mode selection 0, 1, 2, 3, 4, 6, 7
1 0 313
Func-
tion
Parameter
Name Setting Range
Minimum
Setting
Increments
Initial Value
Refer
to
Page
Customer
Setting