Mitsubishi Electronics FR-A720-0.4k to 90k Marine Battery User Manual


 
83
Parameter List
Parameter List
4
PARAMETERS
Control system functions
877
Speed feed forward control/model
adaptive speed control selection
0, 1, 2
1 0 112
878
Speed feed forward filter 0 to 1s
0.01s 0s 112
879
Speed feed forward torque limit 0 to 400%
0.1% 150% 112
880
Load inertia ratio 0 to 200 times
0.1 times
7 times
105,
112
881
Speed feed forward gain 0 to 1000%
1% 0% 112
Regeneration avoidance function
882
Regeneration avoidance operation
selection
0, 1, 2 1 0 383
883
Regeneration avoidance operation
level
300 to 800V 0.1V
380/760VDC
*5
383
884
Regeneration avoidance at
deceleration detection sensitivity
0 to 5
1 0 383
885
Regeneration avoidance compensation
frequency limit value
0 to 10Hz, 9999
0.01Hz 6Hz 383
886
Regeneration avoidance voltage gain 0 to 200%
0.1% 100% 383
Free
parameters
888
Free parameter 1 0 to 9999
1 9999 392
889
Free parameter 2 0 to 9999
1 9999 392
Energy saving monitor
891
Cumulative power monitor digit shifted
times
0 to 4, 9999 1 9999 279
892 Load factor 30 to 150% 0.1% 100% 279
893
Energy saving monitor reference
(motor capacity)
0.1 to 55/0 to 3600kW *2
0.01/
0.1kW
*2
Inverter
rated
capacity
279
894
Control selection during commercial
power-supply operation
0, 1, 2, 3
1 0 279
895 Power saving rate reference value 0, 1, 9999 1 9999 279
896
Power unit cost 0 to 500, 9999
0.01 9999 279
897
Power saving monitor average time 0, 1 to 1000h, 9999
1h 9999 279
898
Power saving cumulative monitor clear 0, 1, 10, 9999
1 9999 279
899 Operation time rate (estimated value) 0 to 100%, 9999 0.1% 9999 279
Calibration parameters
C0
(900)
*7
FM terminal calibration
263
C1
(901)
*7
AM terminal calibration
263
C2
(902)*7
Terminal 2 frequency setting bias
frequency
0 to 400Hz
0.01Hz 0Hz 294
C3
(902)
*7
Terminal 2 frequency setting bias 0 to 300% 0.1% 0% 294
125
(903)
*7
Terminal 2 frequency setting gain
frequency
0 to 400Hz
0.01Hz 60Hz 294
C4
(903)*7
Terminal 2 frequency setting gain 0 to 300%
0.1% 100% 294
C5
(904)
*7
Terminal 4 frequency setting bias
frequency
0 to 400Hz 0.01Hz 0Hz 294
C6
(904)
*7
Terminal 4 frequency setting bias 0 to 300%
0.1% 20% 294
126
(905)*7
Terminal 4 frequency setting gain
frequency
0 to 400Hz
0.01Hz 60Hz 294
C7
(905)
*7
Terminal 4 frequency setting gain 0 to 300% 0.1% 100% 294
Func-
tion
Parameter
Name Setting Range
Minimum
Setting
Increments
Initial Value
Refer
to
Page
Customer
Setting