(2) IPM parameter initialization list
The parameter settings in the following table are changed to the settings required to perform PM sensorless
vector control by selecting PM sensorless vector control with the IPM parameter initialization mode on the
operation panel or with Pr. 998 IPM parameter initialization setting. The changed settings differ according to the
IPM motor specification (capacity).
Performing parameter clear or all parameter clear sets back the parameter settings to the settings required to
drive a general-purpose motor.
*1 Initial values differ according to the inverter capacity. (55K or lower/75K or higher)
*2 Setting Pr. 71 Applied motor = one of "333, 334, 8093, 8094" does not change the Pr. 71 Applied motor setting.
*3 Setting Pr. 80 Motor capacity "9999" does not change the Pr. 80 Motor capacity setting.
*4 This parameter can be set when FR-A7NL is mounted.
*5 200r/min when Pr. 788 Low-speed range torque characteristics = "0".
*6 13.33Hz when Pr. 788 Low-speed range torque characteristics = "0".
Parameter
Name
Setting
Setting
increments
General-
purpose motor
IPM motor
(rotations per minute)
IPM motor
(frequency)
Pr.998
0
(Initial setting)
3003
(MM-CF)
8009 (other
than MM-CF)
3103
(MM-CF)
8109 (other
than MM-CF)
3003,
8009
0, 3103,
8109
1
Maximum frequency 120/60Hz *1 3000r/min 200Hz 1r/min 0.01Hz
4
Multi-speed setting (high speed)
60Hz 2000r/min Pr. 84 133.33Hz Pr. 84 1r/min 0.01Hz
9
Electronic thermal O/L relay
Rated inverter
current
Rated motor
current
(Refer to
page 16
)
Rated motor
current
(Refer to
page 16
)
0.01A/0.1A *1
13
Starting frequency 0.5Hz 8r/min *5 Pr. 84 10% 0.5Hz *6 Pr. 84 10% 1r/min 0.01Hz
15
Jog frequency 5Hz 200r/min Pr. 84 10% 13.33Hz Pr. 84 10% 1r/min 0.01Hz
18
High speed maximum frequency
120/60Hz *1 3000r/min 200Hz 1r/min 0.01Hz
20
Acceleration/deceleration
reference frequency
60Hz 2000r/min Pr. 84 133.33Hz Pr. 84 1r/min 0.01Hz
22
Stall prevention operation level
150% 150% 0.1%
37
Speed display 0 0 1
55
Frequency monitoring reference
60Hz 2000r/min Pr. 84 133.33Hz Pr. 84 1r/min 0.01Hz
56
Current monitoring reference
Rated inverter
current
Rated motor
current
(Refer to
page 16
)
Pr. 859
Rated motor
current
(Refer to
page 16
)
Pr. 859 0.01A/0.1A *1
71
Applied motor 0 330 *2 330 *2 1
80
Motor capacity 9999
Motor capacity
(MM-CF)
*3
Motor capacity
(MM-CF)
*3
0.01kW/0.1kW
*1
81
Number of motor poles 9999 8 8 1
84
Rated motor frequency 60Hz 2000r/min 133.33Hz 1r/min 0.01Hz
125 (903)
Terminal 2 frequency setting
gain frequency
60Hz 2000r/min Pr. 84 133.33Hz Pr. 84 1r/min 0.01Hz
126 (905)
Terminal 4 frequency setting
gain frequency
60Hz 2000r/min Pr. 84 133.33Hz Pr. 84 1r/min 0.01Hz
144
Speed setting switchover 4 108 Pr. 81 +100 8 Pr. 81 1
240
Soft-PWM operation selection 1 0 1
263
Subtraction starting frequency 60Hz 2000r/min Pr. 84 133.33Hz Pr. 84 1r/min 0.01Hz
266
Power failure deceleration
time switchover frequency
60Hz 2000r/min Pr. 84 133.33Hz Pr. 84 1r/min 0.01Hz
374
Overspeed detection level 140Hz 3150r/min
Pr. 1 (Pr. 18) 
105%
210Hz
Pr. 1 (Pr. 18) 
105%
1r/min 0.01Hz
386
Frequency for maximum input pulse
60Hz 2000r/min Pr. 84 133.33Hz Pr. 84 1r/min 0.01Hz
390 *4
% setting reference frequency 60Hz 133.33Hz Pr. 84 133.33Hz Pr. 84 0.01Hz
505
Speed setting reference 60Hz 133.33Hz Pr. 84 133.33Hz Pr. 84 0.01Hz
557
Current average value
monitor signal output
reference current
Rated inverter
current
Rated motor
current
(Refer to
page 16
)
Pr. 859
Rated motor
current
(Refer to
page 16
)
Pr. 859 0.01A/0.1A *1
820
Speed control P gain 1 60% 30% 1%
821
Speed control integral time 1 0.333s 0.333s 0.001s
824
Torque control P gain 1 100% 100% 1%
825
Torque control integral time 1 5ms 20ms 0.1ms
870
Speed detection hysteresis 0Hz 8r/min 0.5Hz 1r/min 0.01Hz
885
Regeneration avoidance
compensation frequency limit value
6Hz 200r/min Pr. 84 10% 13.33Hz Pr. 84 10% 1r/min 0.01Hz
893
Energy saving monitor
reference (motor capacity)
Rated inverter
capacity
Motor capacity (Pr. 80)
0.01kW/0.1kW
*1
C14 (918)
Terminal 1 gain frequency (speed)
60Hz 2000r/min Pr. 84 133.33Hz Pr. 84 1r/min 0.01Hz
: The setting does not change.
REMARKS
If IPM parameter initialization is performed in rotations per minute (Pr. 998 = "3003" or "8009"), the parameters not
listed in the table above are also set and displayed in rotations per minute.
bcnc22005634.fm 6 ページ 2012年7月3日 火曜日 午前9時43分