Mitsubishi Electronics FR-A720-0.4k to 90k Marine Battery User Manual


 
19
Main circuit terminal specifications
2
WIRING
2.2.3 Cables and wiring length
(1) Applied cable size
Select the recommended cable size to ensure that a voltage drop will be 2% max.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor
torque to decrease especially at the output of a low frequency.
The following table indicates a selection example for the wiring length of 20m.
200V class (when input power supply is 220V)
400V class (when input power supply is 440V)
Applicable Inverter
Model
Terminal
Screw
Size *4
Tightening
Torque
N·m
Crimping
Terminal
Cable Sizes
HIV, etc. (mm
2
) *1
AWG/MCM *2
PVC, etc. (mm
2
) *3
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W P/+, P1
Earthing
(grounding)
cable
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W
Earthing
(grounding)
cable
FR-A720-0.4K to
2.2K
M4 1.5 2-4 2-4 2 2 2 2 14 14 2.5 2.5 2.5
FR-A720-3.7K M4 1.5 5.5-4 5.5-4 3.5 3.5 3.5 3.5 12 12 4 4 4
FR-A720-5.5K M5(M4) 2.5 5.5-5 5.5-5 5.5 5.5 5.5 5.5 10 10 6 6 6
FR-A720-7.5K M5(M4) 2.5 14-5 8-5 14 8 14 5.5 6 8 16 10 16
FR-A720-11K M5 2.5 14-5 14-5 14 14 14 14 6 6 16 16 16
FR-A720-15K M6 4.4 22-6 22-6 22 22 22 14 4 4 25 25 16
FR-A720-18.5K M8(M6) 7.8 38-8 38-8 38 38 38 22 2 2 35 35 25
FR-A720-22K M8(M6) 7.8 38-8 38-8 38 38 38 22 2 2 35 35 25
FR-A720-30K M8(M6) 7.8 60-8 60-8 60 60 60 22 1/0 1/0 50 50 25
FR-A720-37K M10(M8) 14.7 80-10 80-10 80 80 80 22 3/0 3/0 70 70 35
FR-A720-45K M10(M8) 14.7 100-10 100-10 100 100 100 38 4/0 4/0 95 95 50
FR-A720-55K M12(M8) 24.5 100-12 100-12 100 100 100 38 4/0 4/0 95 95 50
FR-A720-75K
M12
(
M10
) 24.5 150-12 150-12 125 125 125 38 250 250 ⎯⎯⎯
FR-A720-90K
M12
(
M10
) 24.5 150-12 150-12 150 150 150 38 300 300 ⎯⎯⎯
Applicable Inverter
Model
Terminal
Screw
Size *4
Tightening
Torque
N·m
Crimping
Terminal
Cable Sizes
HIV, etc. (mm
2
) *1
AWG/MCM *2
PVC, etc. (mm
2
) *3
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W P/+, P1
Earthing
(grounding)
cable
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W
Earthing
(grounding)
cable
FR-A740-0.4K to
3.7K
M4 1.5 2-4 2-4 2 2 2 2 14 14 2.5 2.5 2.5
FR-A740-5.5K M4 1.5 2-4 2-4 2 2 3.5 3.5 12 14 2.5 2.5 4
FR-A740-7.5K M4 1.5 5.5-4 5.5-4 3.5 3.5 3.5 3.5 12 12 4 4 4
FR-A740-11K M5 2.5 5.5-5 5.5-5 5.5 5.5 5.5 8 10 10 6 6 10
FR-A740-15K M5 2.5 8-5 8-5 8 8 8 8 8 8 10 10 10
FR-A740-18.5K M6 4.4 14-6 8-6 14 8 14 14 6 8 16 10 16
FR-A740-22K M6 4.4 14-6 14-6 14 14 22 14 6 6 16 16 16
FR-A740-30K M6 4.4 22-6 22-6 22 22 22 14 4 4 25 25 16
FR-A740-37K M8 7.8 22-8 22-8 22 22 22 14 4 4 25 25 16
FR-A740-45K M8 7.8 38-8 38-8 38 38 38 22 1 2 50 50 25
FR-A740-55K M8(M10) 7.8 60-8 60-8 60 60 60 22 1/0 1/0 50 50 25
FR-A740-75K M10 14.7 60-10 60-10 60 60 60 38 1/0 1/0 50 50 25
FR-A740-90K M10 14.7 60-10 60-10 60 60 80 38 3/0 3/0 50 50 25
FR-A740-110K
M10
(
M12)
14.7 80-10 80-10 80 80 80 38 3/0 3/0 70 70 35
FR-A740-132K
M10
(
M12)
14.7 100-10 100-10 100 100 100 38 4/0 4/0 95 95 50
FR-A740-160K
M12
(
M10)
24.5 150-12 150-12 125 150 150 38 250 250 120 120 70
FR-A740-185K
M12
(
M10)
24.5 150-12 150-12 150 150 150 38 300 300 150 150 95
FR-A740-220K
M12
(
M10)
46 100-12 100-12 2×100 2×100 2×100 60 2×4/0 2×4/0 2×95 2×95 95
FR-A740-250K
M12
(
M10)
46 100-12 100-12 2×100 2×100 2×125 60 2×4/0 2×4/0 2×95 2×95 95
FR-A740-280K
M12
(
M10)
46 150-12 150-12 2×125 2×125 2×125 60 2×250 2×250 2×120 2×120 120
FR-A740-315K
M12
(
M10)
46 150-12 150-12 2×150 2×150 2×150 100 2×300 2×300 2×150 2×150 150
FR-A740-355K
M12
(
M10)
46 C2-200
C2-200
2×200 2×200 2×200 100 2×350 2×350 2×185 2×185 2×95
FR-A740-400K
M12
(
M10)
46 C2-200
C2-200
2×200 2×200 2×200 100 2×400 2×400 2×185 2×185 2×95
FR-A740-450K
M12
(
M10)
46 C2-250
C2-250
2×250 2×250 2×250 100 2×500 2×500 2×240 2×240 2×120
FR-A740-500K
M12
(
M10)
46 C2-200
C2-250
3×200 2×250 3×200 2×100 2×500 2×500 2×240 2×240 2×120