Mitsubishi Electronics FR-A720-0.4k to 90k Marine Battery User Manual


 
22/24 BCN-C22005-634
(2) List of automatically-set parameters
The following tables show which parameters are changed in each of the automatic parameter settings.
GOT initial setting (PU connector) (Pr.999 = "10")
GOT initial setting (RS-485 terminals) (Pr.999 = "11")
CAUTION
If the automatic setting is performed with Pr.999 or the automatic parameter setting mode, the listed settings including
the changed parameter settings (changed from the initial setting) will be automatically changed. Before performing
the automatic setting, confirm that changing the listed parameters will not cause any problem.
Parameter Name
Initial
value
Automatically set to Refer to
79 Operation mode selection 01
Chapter 4 of the
Instruction Manual
(Applied)
118 PU communication speed 192 192
119 PU communication stop bit length 110
120 PU communication parity check 21
121
Number of PU communication
retries
19999
122
PU communication check time
interval
9999 9999
123
PU communication waiting time
setting
9999 0ms
124 PU communication CR/LF selection 11
340
Communication startup mode
selection
00
REMARKS
Always perform an inverter reset after the initial setting.
Parameter Name
Initial
value
Automatically set to Refer to
79 Operation mode selection 00
Chapter 4 of the
Instruction Manual
(Applied)
332 RS-485 communication speed 96 192
333
RS-485 communication stop bit
length
110
334
RS-485 communication parity check
selection
21
335 RS-485 communication retry count 19999
336
RS-485 communication check time
interval
0s 9999
337
RS-485 communication waiting time
setting
9999 0ms
340
Communication startup mode
selection
01
341
RS-485 communication CR/LF
selection
11
549 Protocol selection 00
REMARKS
Always perform an inverter reset after the initial setting.
bcnc22005634.fm 22 ページ 2012年7月3日 火曜日 午前9時43分